E6581381
6.17.13 Trip at VIA low level input mode
H : Trip at VIA low level input mode
•Function
The inverter will trip if the VIA value remains below the specified value for about 0.3 seconds. In such a case, "G" is displayed.
H=0: Disabled | The detection function is disabled. |
The inverter will trip if the VIA value remains below the specified value for about | |
| 0.3 seconds. |
Title
Adjustment range
Default setting
H | Trip at VIA low level input mode | 0: Disabled | 0 | |
|
|
|
Note : The VIA input value may be judged earlier to be abnormal, depending on the degree of deviation of the analog data detected.
6.17.14 Parts replacement alarms
| : Annual average ambient temperature (For parts replacement alarms) | 6 |
H |
| |
|
|
|
•Function
You can set the inverter so that it will calculate the remaining useful lives of the cooling fan, main circuit capacitor and
Title | Function | Adjustment range | Default setting |
|
| 1: |
|
| Annual average ambient temperature | 2: 11 to 20°C |
|
H | 3: 21 to 30°C | 3 | |
(For parts replacement alarms) | 4: 31 to 40°C | ||
|
| 5: 41 to 50°C |
|
|
| 6: 51 to 60°C |
|
+Display of part replacement alarm information
Part replacement alarm information (⇒ See page
An example of display: O___
+Output of part replacement alarm signal
Assign the part replacement alarm function (function No. 44 or 45. ⇒ See page
An example of setting: To assign the function to the
Note 1: Using Henter the annual average temperature around the inverter. Be careful not to enter the annual highest temperature
Note 2: Set H at the time of installation of the inverter, and do not change its setting after the start of use. Changing the setting may cause parts replacement alarm calculation error.