Toshiba VF-FS1 + Motor constant must be set, Energy-saving, Operating a permanent magnet motor

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 87
Image 87

E6581381

+Motor constant must be set

If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter,

there is basically no need to set the motor constant. In any other case, be sure to set the parameters H

to H properly.

 

Be sure to set H (rated current of motor) and H (rated speed of motor) correctly, as specified on

the motor’s nameplate. For the setting of H (no-load current of motor), refer to the motor test report.

There are two procedures for setting the other motor constants.

1)

The motor constant can be automatically set (auto-tuning).

 

Set the extended parameter H to .

For details, see selection 1 in 6.15.1.

2)

Each motor constant can be set individually.

For details, see selection 2 in 6.15.1.

5)

Energy-saving

 

 

Setting of V/F control mode selection RV to  (Energy-saving)

 

 

 

Energy can be saved in all speed areas by detecting load current and flowing the optimum current that fits

 

 

the load.

 

+ Motor constant must be set

 

 

If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter,

5

 

there is no need to set the motor constant. In any other case, be sure to set the parameters H to

H properly.

Be sure to set H (rated current of motor) and H (rated speed of motor) correctly, as specified on the motor’s nameplate. For the setting of H (no-load current of motor), refer to the motor test report. There are two procedures for setting the other motor constants.

1)The motor constant can be automatically set (auto-tuning). Set the extended parameter H to .

For details, see selection 1 in 6.15.1.

2) Each motor constant can be set individually.

For details, see selection 2 in 6.15.1.

6) Operating a permanent magnet motor

Setting of V/F control mode selection RV to  (PM motor control)

Permanent magnet motors (PM motors) that are light, small in size and highly efficient, as compared to induction motors, can be operated in sensor-less operation mode.

Note that this feature can be used only for specific motors. For more information, contact your Toshiba dealer.

7)Precautions on vector control

1)When exercising vector control, be sure to set the extended parameters H to H properly. Be sure to set H (rated current of motor) and H (rated speed of motor) correctly, as specified on the motor’s nameplate. For the setting of H (no-load current of motor), refer to the motor test report.

2)The sensorless vector control exerts its characteristics effectively in frequency areas below the base frequency (XN). The same characteristics will not be obtained in areas above the base frequency.

3)Set the base frequency to anywhere from 40 to 120Hz during vector control (RV=).

4)Use a general purpose squirrel-cage motor with a capacity that is the same as the inverter's rated capacity or one rank below.

The minimum applicable motor capacity is 0.1kW.

E-21