E6581381

EOQF : Command mode selection

HOQF : Frequency setting mode selection 1

Function

Remote mode selection, these parameters are used to specify which input device (operation panel, terminal board, serial communication) takes priority in entering an operation stop command or a frequency setting command, VIA, VIB, operation panel, serial communication device, external contact up/down).

At Local mode selection, the start/stop operation and frequency setting by operation panel is prior with no relation of EOQF/HOQFsetting.

<Command mode selection>

Title

Function

Adjustment range

Default setting

 

 

0: Terminal board

 

EOQF

Command mode selection

1: Operation panel

0

 

 

2: Serial communication

 

5

Programmed value

 

 

 

 

 

 

 

 

 

 

 

 

:

Terminal board

ON and OFF of an external signal Runs and stops operation.

 

 

operation

 

 

 

 

 

 

 

 

:

Operation panel

Press the

RUN

and

STOP

keys on the operation panel to start and stop.

 

operation

 

 

 

 

 

 

 

 



Serial communication

Run and stop through serial communication.

 

operation

 

 

 

 

 

 

 

*There are two types of function: the function that conforms to commands selected by EOQF, and the function that conforms only to commands from the terminal board.

See the table of input terminal function selection in Chapter 11.

*When priority is given to commands from a linked computer or terminal board, they have priority over the setting of EOQF.

E-8

Page 74
Image 74