E6581381
■Table of output terminal functions 1
Function | Code | Function | Action |
|
|
No. |
|
|
|
|
|
0 | LL | Frequency lower limit | ON: The output frequency is above the NN set |
|
|
|
|
| value. |
|
|
|
|
| OFF: The output frequency is equal to or less than |
|
|
|
|
| the NN set value. |
|
|
1 | LLN | Inversion of frequency lower limit | Inversion of LL setting |
|
|
2 | UL | Frequency upper limit | ON: Output frequency is equal to or higher than |
|
|
|
|
| WN value. |
|
|
|
|
| OFF: Output frequency is lower than WN value. |
|
|
3 | ULN | Inversion of frequency upper limit | Inversion of UL setting |
|
|
4 | LOW | ON: Output frequency is equal to or higher than |
|
| |
|
|
| H value. |
|
|
|
|
| OFF: Output frequency is lower than H |
|
|
|
|
| value. |
|
|
5 | LOWN | Inversion of | Inversion of LOW setting |
|
|
6 | RCH | Designated frequency attainment signal | ON: The output frequency is equal to or less than |
|
|
|
| (completion of acceleration/deceleration) | the specified frequency ± frequency set with |
|
|
|
|
| H. |
|
|
|
|
| OFF: The output frequency is above the specified |
|
|
|
|
| frequency ± frequency set with H. |
|
|
7 | RCHN | Inversion of designated frequency attainment | Inversion of RCH setting |
|
|
|
| signal (inversion of completion of |
|
|
|
|
| acceleration/deceleration) |
|
|
|
8 | RCHF | Set frequency attainment signal | ON: The output frequency is equal to or less than |
|
|
|
|
| the frequency set with H ± H. |
|
|
|
|
| OFF: The output frequency is above the frequency |
|
|
|
|
| set with H ± H. |
|
|
9 | RCHFN | Inversion of set frequency attainment signal | Inversion of RCHF setting |
|
|
10 | FL | Failure signal (trip output) | ON: When inverter is tripped |
|
|
|
|
| OFF: When inverter is not tripped |
|
|
11 | FLN | Inversion of failure signal (inversion of trip output) | Inversion of FL setting |
|
|
12 | OT | ON: Torque current is equal to or larger than |
|
| |
|
|
| H set value and longer than H |
|
|
|
|
| set time. |
|
|
|
|
| OFF: The torque current is equal to or less than |
|
|
|
|
| (H set value - H set value). |
|
|
13 | OTN | Inversion of | Inversion of OT |
|
|
14 | RUN | Start/Stop | ON: When operation frequency is output or during |
|
|
|
|
| (FD) |
|
|
|
|
| OFF: Operation stopped |
|
|
15 | RUNN | Inversion of RUN/STOP | Inversion of RUN setting |
|
|
16 | POL | OL | ON: 50% or more of calculated value of overload |
|
|
|
|
| protection level |
|
|
|
|
| OFF: Less than 50% of calculated value of |
|
|
|
|
| 11 | ||
|
|
| overload protection level |
| |
17 | POLN | Inversion of OL | Inversion of POL setting |
|
|
20 | POT | ON: Torque current is equal to or larger than 70% |
|
| |
| |||||
|
|
| of H set value. |
|
|
|
|
| OFF: The torque current is below (H set |
|
|
|
|
| value x 70% - H set value). |
|
|
21 | POTN | Inversion of | Inversion of POT setting |
|
|
22 | PAL | One of the following is turned on: |
|
| |
|
|
| ON POL, POT, MOFF, UC, OT, LL stop, COT, |
|
|
|
|
| and instantaneous power failure coast stop. |
|
|
|
|
| or E,R,J issues an alarm |
|
|
|
|
| All the following are turned off: |
|
|
|
|
| OFF POL, POT, MOFF, UC, OT, LL stop, |
|
|
|
|
| COT, and instantaneous power failure coast |
|
|
|
|
| stop. |
|
|
|
|
| or E,R,J issues no alarm |
|
|