E6581381
6.6Operation frequency
6.6.1Starting frequency
H : Starting frequency setting
•Function
The frequency set with H is put out as soon as operation is started.
Use the H parameter when a delay in response of starting torque according to the acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title | Function | Adjustment range | Default setting |
H | Starting frequency setting | 0.5 |
6
6.6.2Run/stop control with frequency setting signals
H : Operation starting frequency
H : Operation starting frequency hysteresis
•Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title | Function | Adjustment range | Default setting |
H | Operation starting frequency | 0.0 | |
H | Operation starting frequency hysteresis | 0.0 |
Output frequency [Hz]
HJ
H + H
H
H - H
The inverter begins accelerating after the frequency setting signal has reached point B.
Deceleration begins when the frequency setting signal decreases below point A.
0 | A | B | 100% Frequency command value |