Toshiba VF-FS1 instruction manual Changing the unit to a,  Current / voltage unit

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 167
Image 167

E6581381

6.20.2 Changing the unit to A / V

H :Current / voltage unit

Function

These parameters are used to change the unit of monitor display.

%A (ampere) / V (volt)

Example of setting

During the operation of the VFFS1-2037PM (rated current: 17.5A) at the rated load (100% load), units are displayed as follows:

1) Display in percentage terms

E 

%Output current:

 

100%

 

%DC voltage:

 

[ 

 

100%

2) Display in amperes/volts

E.

Output current:

 

17.5A

 

DC voltage:

 

[

200V (value

converted into

 

AC)

Title

Function

Adjustment range

Default setting

H

Current/voltage

0: %

0

 

display mode

1: A (ampere)/V (volt)

 

6

*The H converts the following parameter settings:

A display

Current monitor display

 

 

 

Motor electronic-thermal protection level 1 and 2

 

 

 

VJT, H

 

 

DC braking current

H

 

 

Stall prevention level 1 and 2

H, H

 

 

Small current detection current

H

 

 

Step-out detection current level

H

 

 

(for PM motors)

 

V display

Voltage monitor display

 

Note: Base frequency voltage 1 and 2 I(XNX, H)s always displayed in the unit of V.

F-71

Page 167
Image 167
Toshiba VF-FS1 instruction manual Changing the unit to a,  Current / voltage unit