E6581381

[Parameter setting]

 

 

 

 

 

Title

 

Function

Adjustment range

Default setting

 

H

VIA input point 1 setting

0-100 (%)

 

0

 

H

VIA input point 1 frequency

0.0-200.0 (Hz)

 

0.0

 

H

VIA input point 2 setting

0-100 (%)

 

100

 

H

VIA input point 2 frequency

0.0-200.0 (Hz)

50.0

(WP type)

 

60.0

(WN type)

 

 

 

 

 

 

H

VIB input point 1 setting

0-100 (%)

 

0

 

H

VIB input point 1 frequency

0.0-200.0 (Hz)

 

0.0

 

H

VIB input point 2 setting

0-100 (%)

 

100

 

H

VIB input point 2 frequency

0.0-200.0 (Hz)

50.0

(WP type)

 

60.0

(WN type)

 

 

 

 

 

 

H

Communication command point 1 setting

0-100 (%)

 

0

 

H

Communication command point 1 frequency

0.0-200.0 (Hz)

 

0.0

 

H

Communication command point 2 setting

0-100 (%)

 

100

 

H

Communication command point 2 frequency

0.0-200.0 (Hz)

50.0

(WP type)

 

60.0

(WN type)

 

 

 

 

 

Note: Don't set the same value between point 1 and point 2. If set the same falue, the GTT is displayed.

1) 0-10Vdc voltage input adjustment (VIA, VIB)

6

VIA, VIB terminals

H/H

60 ( Hz )

Output frequency

H/H

0 ( Hz)

H/H 0 (%)

0

The output frequency with respect to the voltage input is adjusted according to the selected reference point.

Gradient and bias can be set easily.

H/H 100 (%)

10V voltage signal

Frequency commnd

2) 4-20mAdc current input adjustment (VIA: VIA (SW3) slide switch in the I position)

VIA terminal

H

60 ( Hz )

Output frequency

H

0 ( Hz)

H 20 (%) 4

Frequency commnd

The output frequency with respect to the current input is adjusted according to the selected reference point.

Gradient and bias can be set easily. Set H to  to create a current

input from 0 to 20mA.

H

100 (%)

20mA current signal

F-17

Page 113
Image 113
Toshiba VF-FS1 instruction manual 10Vdc voltage input adjustment VIA, VIB, VIA, VIB terminals