E6581381

6.5.3Setting of frequency with the input from an external contact

H : External contact input - UP response time

H : External contact input - UP frequency steps

H : External contact input - DOWN response time

H : External contact input - DOWN frequency steps

H : Initial up/down frequency

H : Change of the initial up/down frequency

Function

These parameters are used to set an output frequency by means of a signal from an external device.

 

 

Title

Function

 

Adjustment range

Default setting

6

 

 

H

External contact input - UP response

0.0

- 10.0 (s)

0.1

 

time

 

 

H

External contact input - UP frequency

0.0

- FH (Hz)

0.1

 

 

 

steps

 

 

 

 

 

H

External contact input - DOWN

0.0

- 10.0 (s)

0.1

 

 

 

response time

 

 

 

 

 

H

External contact input - DOWN

0.0

- FH (Hz)

0.1

 

 

 

frequency steps

 

 

 

 

 

H

Initial up/down frequency

LL - UL (Hz)

0.0

 

 

 

Change of the initial up/down

0: Not changed

 

 

 

H

1: Setting of H changed

1

 

 

frequency

 

 

 

 

when power is turned off

 

*These functions take effect when parameter HOQF (frequency setting mode selection 1) is set to  or parameter H (frequency setting mode selection 2) is set to  is enabled.

Adjustment with continuous signals (Parameter-setting example 1)

Set parameters as follows to adjust the output frequency up or down in proportion to the frequency adjustment signal input time:

Panel frequency incremental gradient = H/H setting time Panel frequency decremental gradient = H/H setting time

Set parameters as follows to adjust the output frequency up or down almost in synchronization with the adjustment by the panel frequency command:

H = H = 1

(HJ/CEE (or H)) (H/H setting time)

(HJ/FGE (or H)) (H/H setting time)

F-18

Page 114
Image 114
Toshiba VF-FS1 instruction manual Setting of frequency with the input from an external contact