6.10 Bumpless operation
H : Bumpless operation selection
•Function
When switching from Remote mode to Local mode using REMLOC key, the status of start and stop, and operating frequency at Remote mode are moved to Local mode.
By contraries, when switching from Local mode to Remote mode, they are not moved to Remote mode.
[Parameter setting]
Title | Function |
| Adjustment range | Default setting |
H | Bumpless operation selection |
| 0: Disabled | 1 |
| 1: Enabled | |||
|
|
|
| |
Example : Remote mode ( EOQF (Terminal board)) |
|
|
REMLOC Key
6
Output frequency
Internal operation command
Remote mode |
| Local mode |
|
|
|
ON
OFF
ON
OFF
ON
OFF
Setting frequency and start/stop status are moved to Local mode when switching from Remote mode to Local mode.
Motor runs continuously like an example.
REMLOC Key
Output frequency
Internal operation command
| Local mode |
|
| Remote mode | ||||||
| ON |
|
|
|
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Set frequency at | |||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| Remote mode | |||
| ON |
|
|
|
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
|
|
|
| ON |
|
|
|
|
|
|
|
|
|
| OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
When switching from Local mode to Remote mode, setting frequency and start/stop status are determined by Remote mode status.
The example shows the motor runs continuously because the Remote mode is “run” status.
To prevent from moving the setting frequency and start/stop status of Remote mode to Local mode, the H is set to “”(Disabled). In this case, REMLOC key is effective only while stopping.