Toshiba VF-FS1 instruction manual Communication function parameters Common serial options

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 175
Image 175

E6581381

+The following are available as common serial optional units:

USB communication conversion unit (Model: USB001Z)

Communication cable (Model: CAB0011 (1m), CAB0013 (3m), CAB0015 (5m))

Internal LonWorks® communication circuit board (Model: ILU007Z)

Internal BACnet® communication circuit board (Model: BCN002Z)

Internal Metasys® N2 communication circuit board (Model: MTS002Z)

Internal Siemens APOGEETM FLN communication circuit board (Model: APG002Z) These internal products require no interconnect cables, because of built-in type.

Communication function parameters (Common serial options)

The data transfer speed, parity type, inverter number, and communication error trip time can be set/edited by operation panel operation or communication function.

Title

Function

Adjustment range

Default setting

H

Communication rate

0: 9600bps

1

1: 19200bps

 

 

 

 

 

0: NON (No parity)

 

H

Parity

1: EVEN (Even parity)

1

 

 

2: ODD (Odd parity)

 

H

Inverter number

0-247

0

H

Communication error trip time

0: Disabled (*)

0

 

 

6

1-100 (s)

 

 

 

 

 

 

 

 

 

H

Communication waiting time

0.00: Regular communication

0.00

 

 

 

 

 

 

0.01-2.00 (s)

 

 

 

 

 

 

 

 

 

 

 

0: Slave (0 Hz command issued in

 

 

 

 

 

 

case the master inverter fails)

 

 

 

 

 

 

1: Slave (Operation continued in

 

 

 

 

 

Setting of master and slave

case the master inverter fails)

 

 

 

 

 

2: Slave (Emergency stop tripping

 

 

 

 

H

for communication between

0

 

 

 

in case the master inverter fails)

 

 

 

 

inverters

 

 

 

 

 

3: Master (transmission of

 

 

 

 

 

 

 

 

 

 

 

 

frequency commands)

 

 

 

 

 

 

4: Master (transmission of output

 

 

 

 

 

 

frequency signals)

 

 

 

 

H

Communication command point 1

0-100 (%)

0

 

 

 

 

setting

 

 

 

 

 

H

Communication command point 1

0-200.0 (Hz)

0.0

 

 

 

 

frequency

 

 

 

 

 

H

Communication command point 2

0-100 (%)

100

 

 

 

 

setting

 

 

 

 

 

H

Communication command point 2

0.0-200.0 (Hz)

50.0 (WP type)

 

 

 

frequency

 

60.0 (WN type)

 

 

 

 

0: Toshiba inverter protocol

 

 

 

 

 

Selection of communication

1: ModbusRTU protocol

 

 

 

 

H

2: Metasys N2 protocol

0

 

 

 

protocol

 

 

 

 

 

3: APOGEE FLN protocol

 

 

 

 

 

 

4: BAC-net protocol

 

 

 

 

F-79

Page 175
Image 175
Toshiba VF-FS1 instruction manual Communication function parameters Common serial options