Toshiba VF-FS1 instruction manual Setting current stall,  Stall prevention level 

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 151
Image 151

E6581381

Function

This parameter allows selection of the appropriate electronic thermal protection characteristics according to the particular rating and characteristics of the motor.

[Parameter setting]

Title

Function

Adjustment range

Default setting

VJT

Motor electronic thermal protection

10-100 (%) / (A)

100

level 1

 

 

 

H

Motor electronic thermal protection

10-100 (%) / (A)

100

level 2

 

 

 

H

Motor 150%-overload time limit

10-2400 (s)

300

H

Motor electric-thermal protection

0: Disabled

0

retention selection

1: Enabled

 

 

For more details, see section 5.12.

Note: The 100% standard value is the rated output current indicated on the nameplate.

6.17.2 Setting current stall

 

 

 

H

: Stall prevention level 1

 

6

 

 

 

 

: Stall prevention level 2

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Caution

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not set the stall prevention level (H) extremely low.

 

 

 

 

 

 

If the stall prevention level parameter (H) is set at or below the no-load current of the motor, the

 

 

 

 

 

 

stall preventive function will be always active and increase the frequency when it judges that

 

 

Prohibited

 

 

 

 

regenerative braking is taking place.

 

 

 

 

 

 

Do not set the stall prevention level parameter (H) below 30% under normal use conditions.

 

 

Function

This parameter adjusts the output frequency by activating a current stall prevention function against a current exceeding the H-specified level.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Stall prevention level 1

10-110 (%) / (A),

110

 

 

111: Deactivated

H

Stall prevention level 2

 

F-55

Page 151
Image 151
Toshiba VF-FS1 instruction manual Setting current stall,  Stall prevention level