10. Peripheral devices
Danger
•When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious injury.
Mandatory
•Connect earth cables securely.
Failure to do so can lead to risk of electric shock or fire in case of a failure or
Be Grounded
10.1 Selection of wiring materials and devices
| Capacity of |
|
| Wire size (See Note 4) |
|
|
| |
Voltage |
| Power circuit | Earth cable |
|
| |||
applicable motor | Inverter model | (mm2) | Note 1) | (mm2) |
|
| ||
class | (kW) |
|
|
|
|
|
|
|
| For | For JAPAN | For | For JAPAN |
|
| ||
|
|
| 523/54 | 523/54 |
|
| ||
| 0.4 | 1.5 | 2 | 2.5 | 2 |
|
| |
| 0.75 | 1.5 | 2 | 2.5 | 2 |
|
| |
| 1.5 | 1.5 | 2 | 2.5 | 2 |
|
| |
| 2.2 | 1.5 | 2 | 2.5 | 2 |
|
| |
4.0 | 2.5 | 2 | 2.5 | 2 |
|
| ||
5.5 | 4 | 3.5 | 4 | 3.5 |
|
| ||
200V class | 7.5 | 6 | 5.5 | 6 | 3.5 |
|
| |
| 11 | 10 | 14 | 10 | 5.5 |
|
| |
| 15 | 16 | 14 | 16 | 5.5 |
|
| |
| 18.5 | 25 | 22 | 16 | 8 |
|
| |
| 22 | 25 | 38 | 16 | 8 |
|
| |
| 30 | 50 | 38 | 25 | 14 |
|
| |
| 0.4 | 1.5 | 2 | 2.5 | 2 |
|
| |
| 0.75 | 1.5 | 2 | 2.5 | 2 |
|
| |
| 10 | |||||||
| 1.5 | 1.5 | 2 | 2.5 | 2 |
| ||
|
|
| ||||||
| 2.2 | 1.5 | 2 | 2.5 | 2 |
|
| |
4.0 | 1.5 | 2 | 2.5 | 2 |
|
| ||
| ||||||||
5.5 | 1.5 | 2 | 2.5 | 2 |
|
| ||
400V class | 7.5 | 1.5 | 2 | 2.5 | 2 |
|
| |
| 11 | 4 | 3.5 | 4 | 3.5 |
|
| |
| 15 | 6 | 5.5 | 6 | 3.5 |
|
| |
| 18.5 | 6 | 5.5 | 6 | 5.5 |
|
| |
| 22 | 10 | 8 | 10 | 5.5 |
|
| |
| 30 | 16 | 14 | 16 | 5.5 |
|
|
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed 30m.
Note 2: For the control circuit, use shielded wires 0.75 mm2 or more in diameter.
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an insulator with a maximum allowable temperature of 75°C) used at an ambient temperature of 40°C or less.
Note 5: If there is a need to bring the inverter into UL compliance, use wires specified in Chapter 9.