10. Peripheral devices

Danger

When using switchgear for the inverter, it must be installed in a cabinet.

Failure to do so can lead to risk of electric shock and can result in death or serious injury.

Mandatory

Connect earth cables securely.

Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric leak.

Be Grounded

10.1 Selection of wiring materials and devices

 

Capacity of

 

 

Wire size (See Note 4)

 

 

 

Voltage

 

Power circuit

Earth cable

 

 

applicable motor

Inverter model

(mm2)

Note 1)

(mm2)

 

 

class

(kW)

 

 

 

 

 

 

 

 

For IEC60364-5-

For JAPAN

For IEC60364-5-

For JAPAN

 

 

 

 

 

523/54

JEAC8001-1995

523/54

JEAC8001-1995

 

 

 

0.4

VFFS1-2004PM

1.5

2

2.5

2

 

 

 

0.75

VFFS1-2007PM

1.5

2

2.5

2

 

 

 

1.5

VFFS1-2015PM

1.5

2

2.5

2

 

 

 

2.2

VFFS1-2022PM

1.5

2

2.5

2

 

 

Three-phase

4.0

VFFS1-2037PM

2.5

2

2.5

2

 

 

5.5

VFFS1-2055PM

4

3.5

4

3.5

 

 

200V class

7.5

VFFS1-2075PM

6

5.5

6

3.5

 

 

 

11

VFFS1-2110PM

10

14

10

5.5

 

 

 

15

VFFS1-2150PM

16

14

16

5.5

 

 

 

18.5

VFFS1-2185PM

25

22

16

8

 

 

 

22

VFFS1-2220PM

25

38

16

8

 

 

 

30

VFFS1-2300PM

50

38

25

14

 

 

 

0.4

VFFS1-4004PL

1.5

2

2.5

2

 

 

 

0.75

VFFS1-4007PL

1.5

2

2.5

2

 

 

 

10

 

1.5

VFFS1-4015PL

1.5

2

2.5

2

 

 

 

 

 

2.2

VFFS1-4022PL

1.5

2

2.5

2

 

 

Three-phase

4.0

VFFS1-4037PL

1.5

2

2.5

2

 

 

 

5.5

VFFS1-4055PL

1.5

2

2.5

2

 

 

400V class

7.5

VFFS1-4075PL

1.5

2

2.5

2

 

 

 

11

VFFS1-4110PL

4

3.5

4

3.5

 

 

 

15

VFFS1-4150PL

6

5.5

6

3.5

 

 

 

18.5

VFFS1-4185PL

6

5.5

6

5.5

 

 

 

22

VFFS1-4220PL

10

8

10

5.5

 

 

 

30

VFFS1-4300PL

16

14

16

5.5

 

 

Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1, V/T2 and W/T3 when the length of each wire does not exceed 30m.

Note 2: For the control circuit, use shielded wires 0.75 mm2 or more in diameter.

Note 3: For grounding, use a cable with a size equal to or larger than the above.

Note 4: The wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an insulator with a maximum allowable temperature of 75°C) used at an ambient temperature of 40°C or less.