6.8Auto-stop in case of lower-limit frequency continuous operation

6.8.1Auto-stop in case of lower-limit frequency continuous operation

H : Auto-stop in case of lower-limit frequency continuous operation

Function

If operation is carried out continuously at a frequency command below the lower-limit frequency (NN) for the period of time set with H, the inverter will automatically slow down the motor to a stop. At that time, “NUVR” is displayed (alternately) on the operation panel.

This function will be canceled if a frequency command above the lower-limit frequency (NN) +0.2Hz.

6

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Auto-stop in case of lower-limit

0.0: Disabled

0.0

frequency continuous operation time

0.1-600.0 (s)

 

 

Output frequency [Hz]

NN+0.2Hz

NN

Time [s]

H H H

 

 

ON

Operation signal (F or R)

OFF

 

 

 

Note: This function is enabled even at the start of operation and during switching between forward and reverse run.