[Using a VF motor (motor for use with inverter)]

Setting of electronic thermal protection characteristics selection QNO

Setting value

Overload protection

Overload stall



{

 

 

 



{

{

 

 

 



 

 

 



{

 

 

 

 

 

{ : valid, : invalid

VF motors (motors designed for use with inverters) can be used in frequency ranges lower than those for standard motors, but their cooling efficiency decreases at frequencies below 6Hz.

Setting of motor electronic thermal protection level 1VJT (Same as H)

If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor

 

is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1 VJT so

 

that it fits the motor's rated current.

 

* If the indications are in percentages (%), then 100% equals the inverter's rated output current (A).

 

5

Output current reduction factor [%]/[A]

 

 

×1.0

 

 

 

 

VJT

 

 

 

 

 

 

 

×0.6

 

 

VJT

 

0 6Hz

Output frequency (Hz)

Setting the motor overload starting level

2) Motor 150%-overload time limit H

Parameter H is used to set the time elapsed before the motor trips under a load of 150% (overload trip QN) within a range of 10 to 2400 seconds.

3) Inverter over load characteristics

Set to protect the inverter unit. Cannot be changed or turned off by parameter setting.

To prevent the inverter overload trip function (QN) from being activated too easily, lower the stall prevention level (H) or increase the acceleration time (CEE) or deceleration time (FGE).