E6581381

Warning:

When setting the V/F control mode selection parameter (RV) to any number between  and , be sure to set at least the following parameters.

H (Motor rated current): See the motor's nameplate.

H (No-load current of motor): Refer to the motor test report.

H (Rated rotational speed of motor): See the motor's nameplate. Set also other torque boost parameters (H to H), as required.

1) Constant torque characteristics

Setting of V/F control mode selection RV to  (V/F constant)

This is applied to load that requires the same torque at low speeds as at rated speeds.

Base frequency voltage

 

 

XNX

 

 

voltage(%)

 

5

Output

 

 

 

XD

 

 

0

 

Output frequency (Hz)

Base frequency

XN

*To increase the torque further, increase the setting value of the manual torque boost XD.

For more details, see 5.11.

2)Setting for fans and pumps

Setting of V/F control mode selection RV to  (variable torque)

This is appropriate for load characteristics of such things as fans, pumps and blowers in which the torque in relation to load rotation speed is proportional to its square.

Base frequency voltage

XNX

XD

voltage(%)

 

 

 

 

 

Output

 

 

 

 

 

0

 

 

 

 

 

 

Output frequency (Hz)

 

 

 

 

 

 

 

 

 

 

 

 

Base frequency

 

 

 

 

 

 

 

 

 

 

 

 

XN

 

 

 

 

 

 

E-19