E6581381
In the case of reverse operation, the 3 wires operation is also possible as well as forward operation by assigning "R (reverse function)" to the "RES" terminal.
Output frequency
| Forward run |
| Operation |
|
| frequency | |
|
|
| |
| 0 |
| command |
|
| Operation | |
|
|
| |
| Reverse run |
| frequency |
|
| command | |
|
|
| |
| HD |
| ON |
|
|
| |
|
|
| OFF |
| F |
| ON |
|
| OFF | |
5 |
|
| |
R |
| ON | |
|
| ||
|
| OFF | |
| Powered |
| ON |
| on |
| |
|
| OFF | |
|
|
| |
|
| Note 1 | Note 2,4 |
|
|
|
Note 4 :
When HD is OFF, any attempt to turn on F or R is ignored. When R is ON, you cannot start operation by turning on HD. Even when both R and HD are ON, you cannot start operation by turning on F. To start operation, turn off F and R temporarily, then turn them back on.
External input UP/DOWN setting (CW=)
Allows setting of frequency with the input from an external contact. Can be applied to changes of frequencies from several locations.
In case of cancelling the frequency UP/DOWN, it is necessary to assign "CLR (frequency UP/DOWN cancellation from external contacts function)" to the "VIA" terminal separately.
⇒See section 6.5.3 for details.
Used for setting frequencies with