6.18 Forced fire-speed control function

H : Forced fire-speed control function

H : Forced fire-speed setting frequency

Function

Forced fire-speed control is used when operating the motor at the specified frequency in case of an emergency. Two kind of operation are selectable by assignment of terminal board function. (1)Input terminal function 52 (FORCE) : Input signal is kept to hold once signal is ON.

 

 

 

 

Motor runs at the speed set by the parameter H.

 

 

 

 

Motor does not stop in the event of the occurrence of a soft fault.

 

 

(2)Input terminal function 53 (FIRE) : Input signal is kept to hold once signal is ON.

 

 

 

 

 

Motor runs at the speed set by the parameter H.

 

 

Note: Both cases need to power off in order to stop.

 

 

 

 

[Parameter setting]

 

 

6

 

 

 

Title

 

Function

Adjustment range

Default setting

 

 

 

 

 

H

 

Forced fire-speed control selection

0: Disabled

0

 

 

 

 

 

 

1: Enabled

 

 

 

 

 

 

 

 

H

 

Forced fire-speed setting frequency

NNWN

50.0

 

 

When setting the parameter “H”, “HKTG” is displayed by pressing ENT key. It can be set by

 

 

continuing the

ENT key for 2 seconds.

 

 

 

 

[Setting the forced operation input terminal (RES-CC)]

 

 

 

 

The control terminal “RES” (The default setting is “4” (reset function)) shall be assigned to “2” (Forced

 

 

operation function ).

 

 

 

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

Setting value

 

 

 

 

 

 

52

 

 

H

 

Input terminal selection 3 (RES)

0 - 71

( Forced

 

 

 

 

 

 

operation 2 )

F-68