E6581381

(2) A signal is sent out when either of the two functions assigned is activated.

Terminal

Title

Function

Adjustment range

Default setting

symbol

 

 

 

 

 

RY - RC

H

Output terminal selection 1A

 

4 (Low-speed

0255

detection signal)

 

 

 

RY - RC

H

Output terminal selection 1B

(See page K-17)

255 (Always ON)

 

 

 

 

 

 

 

 

 

0 : H and H

 

RY - RC

H

Output terminal logic selection

 

0

 

 

 

1 : H or H

 

 

 

 

 

 

+Two different functions can be assigned to terminals RY-RC.

+If parameter H is set to , a signal will be sent out when either of the two functions assigned is activated.

Terminals RY-RC: Send out a signal when either of the functions set with H and H is activated.

+Timing chart

H

ON

6

OFF

H

ON

OFF

RY-RC output

ON

OFF

+Only one function can be assigned to terminals FLA-FLB-FLC at a time.

(3)Holding the output of signals in ON status

+If the conditions for activating the functions assigned to output terminals RY-RC agree with and as a result the output of signals is put in ON status, the output of signals is held ON, even if the conditions change. (Output terminal holding function)

+Assign input terminal function 62 to a contact input terminal available.

■ Input terminal function

Function No.

Code

Function

Action

 

 

Holding of RY-RC terminal

ON: Once turned on, RY-RC is held on.

62

HDRY

OFF: The status of RY-RC changes in real

output

 

 

time according to conditions.

 

 

 

+ Once output terminal RY-RC is turned on when the contact input terminal to which one of the above functions (function 62) is assigned is ON, output terminal RY-RC is held ON.

F-11

Page 107
Image 107
Toshiba VF-FS1 instruction manual Holding the output of signals in on status, Input terminal function, Hdry