| E6581381 |
| <Frequency setting mode selection> |
|
| |
| Title | Function | Adjustment range | Default setting |
|
|
| 1: VIA |
|
|
|
| 2: VIB |
|
| HOQF | Frequency setting mode selection 1 | 3: Operation panel | 1 |
|
|
| 4: Serial communication |
|
|
|
| 5: UP/DOWN from external contact |
|
[Programmed value]
: | VIA input |
: | VIB input |
: Operation panel
A frequency command is set by means of a signal from an external input device (VIA terminal:
An external signal (VIB terminal:
Press the key or the key on either the operation panel or the expansion panel (optional) to set frequency.
: | Communication | Frequencies are set by commands from an external control unit. | 5 |
: | UP/DOWN frequency | Terminals are used to specify an up/down frequency command. |
|
+No matter what value the command mode selection EOQF and the frequency setting mode selection HOQF are set to the control input terminal functions described below are always in operative state.
•Reset terminal (default setting: RES, valid only for tripping)
•Standby terminal (when programmed by programmable input terminal functions).
•External input tripping stop terminal command (when so set using the programmable input terminal function)
+To make changes in the command mode selection EOQF and the frequency setting mode selection 1 HOQF, first stop the inverter temporarily.
■Preset-speed operation
EOQF: Set to (Terminal board).
HOQF: Valid in all setting values.