E6581381
6.12Trip-less intensification
6.12.1Auto-restart (Restart of coasting motor)
H : Auto-restart control selection
|
|
|
|
|
| Caution | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
| • | Stand clear of motors and mechanical equipment | |||
|
|
| |||||
|
|
|
| If the motor stops due to a momentary power failure, the equipment will start suddenly when power is | |||
|
|
|
| restored. | |||
Mandatory |
| This could result in unexpected injury. | |||||
• | Attach warnings about sudden restart after a momentary power failure on inverters, motors and | ||||||
|
|
| |||||
|
|
|
| equipment for prevention of accidents in advance. | |||
|
|
| • | Function | |||
|
|
|
| The H parameter detects the rotating speed and rotational direction of the motor during | |||
|
|
|
| coasting ing the event of momentary power failure, and then after power haas been restored, restarts |
the motor smoothly (motor speed search function). This parameter also allows commercial power
operation to be switched to inverter operation without stopping the motor. |
|
| 6 | ||
During operation, "TVT[" is displayed. |
|
| |||
|
|
|
|
| |
Title | Function | Adjustment range | Default setting |
| |
|
| 0: Disabled |
|
|
|
| 1: At |
|
|
| |
H | 2: When turning | 0 |
|
| |
selection |
|
| |||
|
| 3: At |
|
|
|
|
| 4: At |
|
|
|
*If the motor is restarted in retry mode, this function will operate, regardless of the setting of this parameter.
1)
Input voltage
Motor speed
F or R command
ON OFF
+Setting H to , (): This function operates after power has been restored following detection of an undervoltage by the main circuits and control power.