6.12.4 Avoiding overvoltage tripping

H : Overvoltage limit operation

H : Overvoltage stall protection level

Function

These parameters are used to keep the output frequency constant or increase it to prevent overvoltage tripping in case the voltage in the DC section rises during deceleration or varying speed operation. The deceleration time during overvoltage limit operation may increase above the designated time.

Overvoltage limit operation level

Output

Frequency

DC Voltage H : Over-voltage stall protection level

6

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

0: Enabled

 

 

 

1: Disabled

 

H

Overvoltage limit operation

2: Enabled (Quick

2

 

(Slowdown stop mode selection)

deceleration)

 

 

 

3: Enabled (Dynamic quick

 

 

 

deceleration)

 

H

Overvoltage limit operation level

100-150%

140

+If H is set to  (quick deceleration), the inverter will increase the voltage to the motor (over- excitation control) to increase the amount of energy consumed by the motor when the voltage reaches the overvoltage protection level, and therefore the motor can be decelerated more quickly than normal deceleration.

+If H is set to  (dynamic quick deceleration), the inverter will increase the voltage to the motor (over-excitation control) to increase the amount of energy consumed by the motor as soon as the motor begins to slow down, and therefore the motor can be decelerated still more quickly than quick deceleration.