Toshiba VF-FS1 instruction manual Over-torque trip

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 157
Image 157

 

 

 

 

E6581381

 

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

 

0: Each time (standard pulse)

 

 

 

 

1: Only one time after power is

 

 

H

Detection of output short-circuit during

turned on (standard pulse)

0

 

 

start-up

2: Each time (short-time pulse)

 

 

 

 

3: Only one time after power is

 

 

 

 

turned on (short-time pulse)

 

6.17.9 Over-torque trip

H : Over-torque trip/alarm selection

H : Over-torque detection level

H : Over-torque detection time

H : Over-torque detection level hysteresis

Function

Use the  parameter to trip the inverter or to output the alarm if a torque currrent exceeding the

 

6

H-specified level flows for more than the H-specified time. Trip information is displayed

 

as "QV".

 

 

 

 

 

 

 

 

H=: .......... No tripping (FL relay deactivated).

 

 

 

 

 

An over-torque alarm can be put out by setting the output terminal function selection

 

 

parameter.

 

 

 

 

H=: .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the

 

 

H-specified level has been detected for more than the H-specified time.

 

 

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

H

Over-torque trip/alarm selection

0: Alarm only

0

 

 

1: Tripping

 

 

 

 

 

 

 

H

Over-torque detection level

0-200 (%)

130

 

 

H

Over-torque detection time

0.0-10.0 [s]

0.5

 

 

H

Over-torque detection level hysteresis

0-100 (%)

10

 

 

F-61

Page 157
Image 157
Toshiba VF-FS1 instruction manual Over-torque trip