E6581381

5.4Meter setting and adjustment

HOUN : Meter selection

HO : Meter adjustment

Function

The signal output from the FM terminal is an analog voltage signal.

For the meter, use either a full-scale 0-1mAdc ammeter or full-scale 0-7.5Vdc (or 10Vdc-1mA) voltmeter. Switching to 0-20mAdc (4-20mAdc) output current can be made by turning the FM (SW2) slide switch to the I position. When switching to 4-20mAdc current input, make adjustments using H (analog output gradient) and H (analog output bias).

[Parameter setting]

5

Title

Function

Adjustment range

Supposition output at

Default setting

HOUN=

 

 

 

 

 

 

0: Output frequency

Maximum frequency (HJ)

 

 

 

1: Output current

1.5 times of rated current

 

 

 

2: Set frequency

Maximum frequency (HJ)

 

 

 

3: DC voltage

1.5 times of rated voltage

 

 

 

4: Output voltage command value

1.5 times of rated voltage

 

 

 

5: Input power

1.85 times of rated power

 

 

 

6: Output power

1.85 times of rated power

 

 

 

7: Torque

2.5 times of rated torque

 

 

 

8: Torque current

2.5 times of rated torque

 

 

 

9: Motor cumulative load factor

Rated load factor

 

HOUN

Meter

10: Inverter cumulative load factor

Rated load factor

0

selection

11: - (Do not select)

-

 

 

12: Frequency setting value (after PID)

Maximum frequency (HJ)

 

 

 

13: VIA Input value

Maximum input value

 

 

 

14: VIB Input value

Maximum input value

 

 

 

15: Fixed output 1 (Output current: 100%)

-

 

 

 

16: Fixed output 2 (Output current: 50%)

-

 

 

 

17: Fixed output 3

-

 

 

 

(Supposition output at HOUN=17)

 

 

 

 

18: Serial communication data

FA51=1000

 

 

 

19: For adjustments (HOset value is

-

 

 

 

displayed.)

 

 

HO

Meter

-

-

-

adjustment

 

 

 

 

E-10

Page 76
Image 76