5.4Meter setting and adjustment
HOUN : Meter selection
HO : Meter adjustment
•Function
The signal output from the FM terminal is an analog voltage signal.
For the meter, use either a
[Parameter setting]
5
Title | Function | Adjustment range | Supposition output at | Default setting | |
HOUN= | |||||
|
|
|
| ||
|
| 0: Output frequency | Maximum frequency (HJ) |
| |
|
| 1: Output current | 1.5 times of rated current |
| |
|
| 2: Set frequency | Maximum frequency (HJ) |
| |
|
| 3: DC voltage | 1.5 times of rated voltage |
| |
|
| 4: Output voltage command value | 1.5 times of rated voltage |
| |
|
| 5: Input power | 1.85 times of rated power |
| |
|
| 6: Output power | 1.85 times of rated power |
| |
|
| 7: Torque | 2.5 times of rated torque |
| |
|
| 8: Torque current | 2.5 times of rated torque |
| |
|
| 9: Motor cumulative load factor | Rated load factor |
| |
HOUN | Meter | 10: Inverter cumulative load factor | Rated load factor | 0 | |
selection | 11: - (Do not select) | - | |||
|
| 12: Frequency setting value (after PID) | Maximum frequency (HJ) |
| |
|
| 13: VIA Input value | Maximum input value |
| |
|
| 14: VIB Input value | Maximum input value |
| |
|
| 15: Fixed output 1 (Output current: 100%) | - |
| |
|
| 16: Fixed output 2 (Output current: 50%) | - |
| |
|
| 17: Fixed output 3 | - |
| |
|
| (Supposition output at HOUN=17) |
|
| |
|
| 18: Serial communication data | FA51=1000 |
| |
|
| 19: For adjustments (HOset value is | - |
| |
|
| displayed.) |
|
| |
HO | Meter | - | - | - | |
adjustment | |||||
|
|
|
|