E6581381
■AIC, Fuse and Wire sizes
|
|
| Capacity of |
| AIC (A) |
|
|
|
|
|
| Voltage | applicable |
| Fuse class and | Input wire sizes of | Out put wire sizes |
| |
|
| Inverter model | (Interrupting | Earth | |||||
|
| class | motor |
| capacity) | current (A) | power circuit | of power circuit |
|
|
|
| (kW) |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
| 0.4 | AIC 5000A | J 3A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 0.75 | AIC 5000A | J 6A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 1.5 | AIC 5000A | J 10A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 2.2 | AIC 5000A | J 15A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 4.0 | AIC 5000A | J 25A max. | AWG 12 | AWG 10 | AWG 12 | |
|
| 5.5 | AIC 22000A | J 35A max. | AWG 10 | AWG 8 | AWG 10 | ||
|
| 200V class | 7.5 | AIC 22000A | J 45A max. | AWG 8 | AWG 8 | AWG 10 | |
|
|
| 11 | AIC 22000A | J 70A max. | AWG 6 | AWG 6 | AWG 10 | |
|
|
| 15 | AIC 22000A | J 90A max. | AWG 4 | AWG 4 | AWG 10 | |
|
|
| 18.5 | AIC 22000A | J 100 A max. | AWG 4 | AWG 3 | AWG 8 | |
|
|
| 22 | AIC 22000A | J 125A max. | AWG 2 | AWG 2 | AWG 8 | |
|
|
| 30 | AIC 22000A | J 175A max. | AWG 1/0 | AWG 1/0 | AWG 6 | |
|
|
| 0.4 | AIC 5000A | J 3A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 0.75 | AIC 5000A | J 3A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 1.5 | AIC 5000A | J 6A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 2.2 | AIC 5000A | J 10A max. | AWG 14 | AWG 14 | AWG 14 | |
|
|
| 4.0 | AIC 5000A | J 15A max. | AWG 14 | AWG 14 | AWG 14 | |
|
| 5.5 | AIC 22000A | J 20A max. | AWG 14 | AWG 14 | AWG 14 | ||
|
| 400V class | 7.5 | AIC 22000A | J 25A max. | AWG 12 | AWG 12 | AWG 14 | |
9 |
|
|
|
|
|
|
|
|
|
|
| 11 | AIC 22000A | J 35A max. | AWG 10 | AWG 10 | AWG 10 | ||
|
| 15 | AIC 22000A | J 45A max. | AWG 8 | AWG 8 | AWG 10 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| 18.5 | AIC 22000A | J 60A max. | AWG 8 | AWG 8 | AWG 10 | |
|
|
| 22 | AIC 22000A | J 70A max. | AWG 6 | AWG 6 | AWG 10 | |
|
|
| 30 | AIC 22000A | J 90A max. | AWG 4 | AWG 4 | AWG 10 |
9.2.4Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In case of multi motor operation with one inverter, thermal relay should be connected to each motor.