E6581381

AIC, Fuse and Wire sizes

 

 

 

Capacity of

 

AIC (A)

 

 

 

 

 

 

Voltage

applicable

 

Fuse class and

Input wire sizes of

Out put wire sizes

 

 

 

Inverter model

(Interrupting

Earth

 

 

class

motor

 

capacity)

current (A)

power circuit

of power circuit

 

 

 

 

(kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

VFFS1-2004PM

AIC 5000A

J 3A max.

AWG 14

AWG 14

AWG 14

 

 

 

0.75

VFFS1-2007PM

AIC 5000A

J 6A max.

AWG 14

AWG 14

AWG 14

 

 

 

1.5

VFFS1-2015PM

AIC 5000A

J 10A max.

AWG 14

AWG 14

AWG 14

 

 

 

2.2

VFFS1-2022PM

AIC 5000A

J 15A max.

AWG 14

AWG 14

AWG 14

 

 

 

4.0

VFFS1-2037PM

AIC 5000A

J 25A max.

AWG 12

AWG 10

AWG 12

 

 

Three-phase

5.5

VFFS1-2055PM

AIC 22000A

J 35A max.

AWG 10

AWG 8

AWG 10

 

 

200V class

7.5

VFFS1-2075PM

AIC 22000A

J 45A max.

AWG 8

AWG 8

AWG 10

 

 

 

11

VFFS1-2110PM

AIC 22000A

J 70A max.

AWG 6

AWG 6

AWG 10

 

 

 

15

VFFS1-2150PM

AIC 22000A

J 90A max.

AWG 4

AWG 4

AWG 10

 

 

 

18.5

VFFS1-2185PM

AIC 22000A

J 100 A max.

AWG 4

AWG 3

AWG 8

 

 

 

22

VFFS1-2220PM

AIC 22000A

J 125A max.

AWG 2

AWG 2

AWG 8

 

 

 

30

VFFS1-2300PM

AIC 22000A

J 175A max.

AWG 1/0

AWG 1/0

AWG 6

 

 

 

0.4

VFFS1-4004PL

AIC 5000A

J 3A max.

AWG 14

AWG 14

AWG 14

 

 

 

0.75

VFFS1-4007PL

AIC 5000A

J 3A max.

AWG 14

AWG 14

AWG 14

 

 

 

1.5

VFFS1-4015PL

AIC 5000A

J 6A max.

AWG 14

AWG 14

AWG 14

 

 

 

2.2

VFFS1-4022PL

AIC 5000A

J 10A max.

AWG 14

AWG 14

AWG 14

 

 

 

4.0

VFFS1-4037PL

AIC 5000A

J 15A max.

AWG 14

AWG 14

AWG 14

 

 

Three-phase

5.5

VFFS1-4055PL

AIC 22000A

J 20A max.

AWG 14

AWG 14

AWG 14

 

 

400V class

7.5

VFFS1-4075PL

AIC 22000A

J 25A max.

AWG 12

AWG 12

AWG 14

9

 

 

 

 

 

 

 

 

 

 

 

11

VFFS1-4110PL

AIC 22000A

J 35A max.

AWG 10

AWG 10

AWG 10

 

 

15

VFFS1-4150PL

AIC 22000A

J 45A max.

AWG 8

AWG 8

AWG 10

 

 

 

 

 

 

 

 

 

 

 

 

 

18.5

VFFS1-4185PL

AIC 22000A

J 60A max.

AWG 8

AWG 8

AWG 10

 

 

 

22

VFFS1-4220PL

AIC 22000A

J 70A max.

AWG 6

AWG 6

AWG 10

 

 

 

30

VFFS1-4300PL

AIC 22000A

J 90A max.

AWG 4

AWG 4

AWG 10

9.2.4Motor thermal protection

Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In case of multi motor operation with one inverter, thermal relay should be connected to each motor.

I-6

Page 202
Image 202
Toshiba VF-FS1 instruction manual Motor thermal protection, AIC, Fuse and Wire sizes, AIC a