6.17.4 Emergency stop
H: Emergency stop
H : Emergency DC braking time
•Function
These parameters allow you to specify how to stop operation using an external control device when an external trip occurs. When operation is stopped, the trip G and the FL relay also are activated. When setting H to (emergency DC braking), set also H (DC braking rate) and H (emergency braking time)
1)External trip stop via terminals
The external trip stop function can be executed via the
[Parameter setting] |
|
|
|
|
| |
Title | Function | Adjustment range |
| Default setting |
|
|
|
| 0: Coast stop |
|
|
| 6 |
H | Emergency stop selection | 1: Slowdown stop |
| 0 |
| |
|
| 2: Emergency DC braking |
|
|
|
|
|
|
|
|
|
| |
H | Emergency DC braking time | 0.0 ~ 20.0 [sec] |
| 1.0 |
|
|
H | DC braking current |
| 50 |
|
| |
(Example of terminal assignment): Assigning the trip stop function to the RES terminal |
|
|
|
| ||
Title | Function | Adjustment range |
| Setting value |
|
|
H | Input terminal selection 3 (RES) | 11 (External trip |
|
| ||
| stop) |
|
| |||
|
|
|
|
|
|
Note 1: Emergency stopping via the specified terminal is possible, even during panel operation.
Note 2: If DC braking is not needed to bring the motor to a stop under normal conditions, although H is set to 2 (emergency DC braking), set the DC braking starting frequency (H) at 0.0 Hz.
2) Emergency stopping from the operation panel
Emergency stopping from the operation panel is possible
by pressing the STOP key on the panel twice while the inverter is not in the panel control mode.
(1) | Press the | STOP key | "GQHH" will blink. |
(2) | Press the | STOP key once again | Operation will come to a trip stop in accordance with the setting |
|
|
| of the H parameter. |
After this, "G" will be displayed and a failure detection signal generated (FL relay deactivated).