[Alarm information]

Each message in the table is displayed to give a warning but does not cause the inverter to

 

 

 

trip.

 

 

 

 

 

Error code

 

Problem

 

Possible causes

Remedies

 

 

QHH

ST terminal OFF

The ST-CC circuit is opened.

Close the ST-CC circuit.

 

 

OQHH

Undervoltage in main

The supply voltage between R, S and T is

Measure the main circuit supply voltage.

 

 

 

circuit

 

 

under voltage.

If the voltage is at a normal level, the

 

 

 

 

 

 

 

inverter requires repairing.

 

 

TVT[

Retry in process

The inverter is n the process of retry.

The inverter is normal if it restarts after

 

 

 

 

 

A momentary stop occurred.

several tens of senconds.

 

 

 

 

 

 

 

The inverter restarts automatically. Be

 

 

 

 

 

 

 

careful of the machine because it may

 

 

 

 

 

 

 

suddenly restart.

 

 

GTT

Frequency point

The frequency setting signals at points 1

Set the frequency setting signals at points

 

 

 

setting error alarm

 

and 2 are set too close to each other.

1 and 2 apart from each other.

 

 

ENT

Clear command

This message is displayed when pressing

Press the STOP key again to clear the

 

 

 

acceptable

 

the STOP key while an error code is

trip.

 

 

 

 

 

 

displayed.

 

 

 

GQHH

Emergency stop

The operation panel is used to stop the

Press the STOP key for an emergency

 

 

 

command

 

operation in automatic control or remote

stop.

 

 

 

acceptable

 

control mode.

To cancel the emergency stop, press any

 

 

 

 

 

 

 

other key.

 

 

J/

Setting error alarm /

An error is found in a setting when data is

Check whether the setting is made

 

 

NQ

An error code and

 

reading or writing.

correctly.

 

 

data are displayed

 

 

 

 

 

 

 

 

 

 

 

 

alternately twice

 

 

 

 

 

 

each.

 

 

 

 

 

 

JGCF/

Display of first/last

The first and last data item in the CWJ

Press MODE key to exit the data group.

 

 

GPF

data items

 

data group is displayed.

 

 

 

 

 

 

 

 

 

 

FD

DC braking

DC braking in process

The message goes off in several tens of

 

 

 

 

 

 

 

seconds if no problem occurs. Note)

 

 

FDZP

Shaft fixing control

Motor shaft fixing control is in process.

Normal if the message disappears when

 

 

 

 

 

 

 

a stop command is entered (or the

 

 

 

 

 

 

 

operation command is canceled).

 

 

G

Flowing out of

The number of digits such as frequencies

Lower the fequency free unit

 

 

 

excess number of

 

is more than 4.

magnification H.

 

 

 

digits

 

 

(The upper digits have a priority.)

 

 

 

UVQR

Instantaneous power

The coast stop function set with H

To restart operation, reset the inverter or

 

 

 

failure coast stop

 

(Instantaneous power failure coast stop)

input an operation signal again.

 

 

 

function activated.

 

is activated.

 

 

 

NUVR

Auto-stop because of

The automatic stop function selected with

To deactivate the automatic stop function,

 

 

 

continuous operation

 

H was activated.

increase the frequency command above

 

 

 

at the lower-limit

 

 

the lower-limit frequency (LL) + 0.2 Hz or

 

 

 

frequency

 

 

turn off the operation command.

 

 

KPKV

Parameters in the

Parameters are being initialized to default

Normal if the message disappears after a

 

 

 

process of

 

values.

while (several seconds to several tens of

 

 

 

initialization

 

 

seconds).

 

 

G

Operation panel key

The RUN or STOP key is held down for

Check the operation panel.

 

 

 

fault

 

 

more than 20 seconds.

 

 

 

 

 

 

The RUN or STOP key is faulty.

 

 

 

CVP

Auto-tuning

Auto-tuning in process

Normal if it the message disappears after

 

 

 

 

 

 

 

a few seconds.

 

 

M

Integral input power

Integral input power is more than

Press and hold down the ENT key for 3

 

 

 

 

 

 

999.99kWh.

seconds or more when power is off or

 

 

 

 

 

 

 

when the input terminal function CKWH

 

 

 

 

 

 

 

is turned on or displayed.

 

 

J

Integral output power

Integral output power is more than

Press and hold down the ENT key for 3

 

 

 

 

 

 

999.99kWh.

seconds or more when power is off or

 

 

 

 

 

 

 

when the input terminal function CKWH

 

 

 

 

 

 

 

is turned on or displayed.

 

Note: When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter, you can judge the inverter to be normal if “FD” disappears when opening the circuit between the terminal and CC.

M-4

Page 238
Image 238
Toshiba VF-FS1 instruction manual Qhh