Toshiba VF-FS1 instruction manual Setting of contact input terminal function, Res

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 102
Image 102

E6581381

Function

Use the above parameters to send signals from an external programmable controller to various control input terminals to operate and/or set the inverter.

The desired contact input terminal functions can be selected from 57 types (0 to 71). This gives system design flexibility.

The functions of the VIA terminal can be selected between analog input and contact input by changing parameter settings H.

To use the VIA terminal as contact input terminals, you need to set H to the number (1 or 2) that suits your needs, since analog input (voltage signal input) is assigned to the terminals by default.

Setting of contact input terminal function

 

 

Terminal

Title

Function

 

Adjustment range

 

Default setting

 

 

symbol

 

 

 

 

 

 

 

 

 

 

 

 

-

H

Always-active function selection 1

 

0

 

 

 

 

 

 

 

 

 

 

 

-

H

Always-active function selection 2

 

1

(ST)

 

 

 

 

 

 

0-71

 

 

 

 

F

H

Input terminal selection 1 (F)

2

(F)

 

 

(See page K-15)

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

R

H

Input terminal selection 2

(R)

3

(R)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RES

H

Input terminal selection 3

(RES)

 

10 (RES)

 

 

 

 

 

 

 

 

 

 

 

 

VIA

H

Input terminal selection 8

(VIA)

0-71 Note 2)

6 (SS1)

Note 1: The function that has been selected using H and H (always-active function selection parameter) are always activated.

Note 2: When using the VIA terminal as contact input terminals in sink logic connection, be sure to insert a resistor between the P24 terminal and the VIA terminal. (Recommended resistance: 4.7k-1/2W) Be sure to turn the VIA (SW3) slide switch to the V position.

Note 3: H (VIA): Enabled only when H= or 

Disabled and the set value cannot be read out, if H is set at .

F-6

Page 102
Image 102
Toshiba VF-FS1 instruction manual Setting of contact input terminal function, Res