E6581381
Coast stop (CW=)
Setting for coast stopping. In sink logic mode, closing the circuit between the R and CC terminals places the inverter in standby mode and opening the circuit places it in coast stop mode, because ST (standby signal) is assigned to the R terminal.
⇒See section 3.1.1 (3) and 6.3.1 for details.
Can be operated by a momentary
+
You can carry out operation by simply pressing the ON/OFF button.
Standard connection diagram- Forward run
F
R (HD)
RES
CC
PLC
PP
VIA
VIB
CC | RUN STOP |
Parameter setting: | 5 |
When parameter CWis set to , the following |
parameters are set automatically. H : (ST)
EOQF : (terminal board).
R terminal H : (operation holding).
Note 1 : Even if each terminal is ON, any command entered through a terminal is ignored when power is turned on (to prevent the load from starting to move unexpectedly). Enable to turn the input terminal on at power on.
Note 2 : When HD is OFF, any attempt to turn on F is ignored.
Note 3 : Sending out a RUN signal during DC braking has no effect in stopping DC braking.
Selecting HD (operation holding) with the input terminal selection parameter
Select HD (operation holding) using the input terminal selection parameter, and turn HD on to get the inverter ready for operation or turn HD off to stop operation.