E6581381

6. Extended parameters

Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify parameter settings as required. See section 11, table of extended parameters.

6.1Input/output parameters

6.1.1Low-speed signal

H : Low-speed signal output frequency

Function

When the output frequency exceeds the setting of H an ON signal will be generated. This signal can be used as an electromagnetic brake excitation/release signal.

This signal can also be used as an operation signal when H is set to 0.0Hz, because an ON signal is put out if the output frequency exceeds 0.0Hz.

+ Relay output (250Vac-1A (cosφ=1), 30Vdc-0.5A, 250Vac-0.5A (cosφ=0.4)

 

 

6

at RY-RC, FLA-FLC-FLB terminals.

 

 

 

[Parameter setting]

 

 

 

 

 

Title

 

Function

Adjustment range

Default setting

 

H

Low-speed signal output frequency

0.0 HJ (Hz)

0.0

 

 

Output frequency [Hz]

Set frequency

H

0

Low-speed signal output RY-RC terminals (Default setting) FLA-FLC-FLB terminals

Low-speed signal output:

Inverted

Time [s]

ON

OFF

ON

OFF

F-1

Page 97
Image 97
Toshiba VF-FS1 instruction manual Extended parameters, Input/output parameters,  Low-speed signal output frequency