■Connection method 1) A-contact input
Inverter
Input terminal
CC
Sink setting
*This function is activated when the input terminal and CC (common) are short- circuited. Use this function to specify forward/reverse run or a
2) Connection with transistor output
Inverter
Input terminal
Programmable controller
* Operation can be controlled by connecting the | ||||
input and CC (common) terminals to the | ||||
output | switch) | of | the | |
programmable controller. Use this function to | ||||
specify forward/reverse run or a | ||||
operation. Use a transistor that | operates | at |
CC
24Vdc/5mA. |
* Interface between programmable controller and inverter
6
Note: When using a programmable controller with open collector outputs for control, connect it to the PCL terminal, as shown in the figure below, to prevent the inverter from malfunctioning because of a current that flows in.
Also, be sure to turn the SW4 slide switch to the PLC position.