E6581381
■Setting of electronic thermal protection characteristics selection QNO
Setting value | Overload protection | Overload stall |
{ | ⋅ | |
|
|
|
{ | { | |
|
|
|
⋅ | ⋅ | |
|
|
|
⋅ | { | |
|
|
|
|
| { : valid, ⋅ : invalid |
■Setting of motor electronic thermal protection level 1 VJT (Same as H)
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1 VJT so that it fits the motor's rated current.
Output current reduction factor [%]/[A]
VJT
×1.0
5
VJT
×0.55
0
| 30Hz | Output frequency (Hz) |
Note: | The motor overload protection start level is fixed at 30Hz. |
[Example of setting: When the
Key operated | LED display |
|
|
|
| Operation | |||
|
| Displays the operation frequency. (Perform during operation | |||||||
| stopped.) | ||||||||
| (When standard monitor display selection H is set to | ||||||||
|
| ||||||||
|
| [Operation frequency]) | |||||||
MODE | CWH | The first basic parameter “CWH” (Wizard function) is displayed. | |||||||
|
|
|
|
|
|
|
|
| |
| VJT | Press either the |
| key or the |
| key to change the parameter to | |||
|
|
| |||||||
| VJT. | ||||||||
|
| ||||||||
ENT | Press the ENT key to display the parameter setting. (Standard | ||||||||
default setting: 100%) | |||||||||
|
| ||||||||
|
| Press the |
| key to change the parameter to % | |||||
| (=motor rated current/inverter output rated current x | ||||||||
|
| 100=2.0//4.8×100). |
|
| |||||
ENT | ¶⇔¶VJT | Press the ENT key to save the changed parameter. VJT and the | |||||||
parameter are displayed alternately. |
Note: The rated output current of the inverter should be calculated from the rated current, regardless of the setting of the PWM carrier frequency parameter (H).