Setting of electronic thermal protection characteristics selection QNO

Setting value

Overload protection

Overload stall



{

 

 

 



{

{

 

 

 



 

 

 



{

 

 

 

 

 

{ : valid, : invalid

Setting of motor electronic thermal protection level 1 VJT (Same as H)

If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1 VJT so that it fits the motor's rated current.

Output current reduction factor [%]/[A]

VJT×1.0

5

VJT×0.55

0

 

30Hz

Output frequency (Hz)

Note:

The motor overload protection start level is fixed at 30Hz.

[Example of setting: When the VFFS1-2007PM is running with a 0.4kW motor having 2A rated current]

Key operated

LED display

 

 

 

 

Operation

 

 

Displays the operation frequency. (Perform during operation

 



stopped.)

 

(When standard monitor display selection H is set to 

 

 

 

 

[Operation frequency])

MODE

CWH

The first basic parameter “CWH” (Wizard function) is displayed.

 

 

 

 

 

 

 

 

 

 

VJT

Press either the

 

key or the

 

key to change the parameter to

 

 

 

 

VJT.

 

 

ENT



Press the ENT key to display the parameter setting. (Standard

default setting: 100%)

 

 

 

 

Press the

 

key to change the parameter to %

 



(=motor rated current/inverter output rated current x

 

 

100=2.0//4.8×100).

 

 

ENT

¶¶VJT

Press the ENT key to save the changed parameter. VJT and the

parameter are displayed alternately.

Note: The rated output current of the inverter should be calculated from the rated current, regardless of the setting of the PWM carrier frequency parameter (H).