E6581381

 

 

 

 

(Continued)

 

 

 

 

 

 

 

Error code

Failure code

Problem

 

Possible causes

Remedies

 

 

 

QJ

002E

External thermal trip

An external thermal trip is input.

Check the external thermal input.

 

 

 

 

 

 

PTC protection worked.

Check the PTC in the motor.

 

 

 

G

0011

Emergency stop

During automatic operation or remote

Reset the inverter.

 

 

 

 

 

 

 

operation, a stop command is entered

 

 

 

 

 

 

 

 

from the operation panel or a remote

 

 

 

 

 

 

 

 

input device.

 

 

 

 

GGR

0012

EEPROM fault 1

A data writing error occurs.

Turn off the inverter, then turn it again. If it

 

 

 

 

 

 

 

 

does not recover from the error, make a

 

 

 

 

 

 

 

 

service call.

 

 

 

GGR

0013

EEPROM fault 2

Power supply is cut off during V[R

Turn the power off temporarily and turn it

 

 

 

 

 

 

 

operation and data writing is aborted.

back on, and then try V[R operation

 

 

 

 

 

 

 

 

again.

 

 

 

GGR

0014

EEPROM fault 3

A data reading error occurred.

Turn off the inverter, then turn it again. If it

 

 

 

 

 

 

 

 

does not recover from the error, make a

 

 

 

 

 

 

 

 

service call.

 

 

 

GTT

0015

Main unit RAM fault

The control RAM is defective.

Make a service call.

 

 

 

GTT

0016

Main unit ROM fault

The control ROM is defective.

Make a service call.

 

 

 

GTT

0017

CPU fault 1

The control CPU is defective.

Make a service call.

 

 

 

*

0018

Communication error

An error arises during serial

Check the remote control device, cables,

 

 

 

GTT

 

 

 

communication.

etc.

 

 

 

 

 

 

 

 

 

 

 

GTT

001A

Current detector fault

The current detector is defective.

Make a service call.

 

 

 

GTT

001B

Network error

The error was occurred during Network

Check the Network device and wiring.

 

 

 

 

 

 

 

communication.

 

 

 

 

*

001D

Low-current

The output current decreased to a low-

Enable H (low-current detection).

 

 

 

WE

 

operation

 

current detection level during operation.

Check the suitable detection level for the

 

 

 

 

Trip

 

 

system (H, H).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Make a service call if the setting is

 

 

 

 

 

 

 

 

correct.

 

 

 

*

001E

Undervoltage trip

The input voltage (in the main circuit) is

Check the input voltage.

 

 

 

WR

 

(main circuit)

 

too low.

Enable H (undervoltage trip

 

 

 

 

 

 

 

selection).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To cope with a momentary stop due to

 

 

 

 

 

 

 

 

undervoltage, enable H (coast stop)

 

 

 

 

 

 

 

 

and H (auto-restart).

 

 

 

GH

0022

Ground fault trip

A ground fault occurs in the output cable

Check the cable and the motor for ground

 

 

 

 

 

 

 

or the motor.

faults.

 

 

 

GVP

0054

Auto-tuning error

Check the motor parameter H to H.

 

 

 

 

 

 

The motor with the capacity of 2 classes or less than the inverter is used.

 

 

 

 

 

 

The output cable is too thin.

 

 

 

 

 

 

 

The motor is rotating.

 

 

 

 

 

 

 

The inverter is used for loads other than those of three-phase induction motors.

 

 

 

GV[R

0029

Inverter

Circuit board is changed.

Make a service call.

 

 

 

 

 

type error

 

(Or main circuit/drive circuit board)

 

 

 

 

*

0032

Brea in analog signal

The signal input via VIA is below the

Check the cables for breaks. And check

 

 

 

G

 

cable

 

analog sinal detectio level set with

the setting of input signal or setting value

 

 

 

 

 

 

H.

of H.

 

 

 

 

 

 

 

 

 

 

G

0033

CPU

A communications error occurs between

Make a service call.

 

 

 

 

 

communications

 

control CPUs.

 

 

 

 

 

 

error

 

 

 

 

13

 

G

0034

Excessive torque

The torque boost parameter H is

Re do the Auto-tuning then set H.

 

 

 

 

boosted

 

set too high.

Decrease the setting of the torque boost

 

 

 

 

 

The motor has too small impedance.

parameter H.

 

 

 

G

0035

CPU fault 2

The control CPU is defective.

Make a service call.

 

 

 

UQWV

002F

Step-out

The motor shaft is locked.

Unlock the motor shaft.

 

 

 

 

 

(For PM motor only)

One output phase is open.

Check the interconnect cables between

 

 

 

 

 

 

An impact load is applied.

the inverter and the motor.

 

 

*You can select a trip ON/OFF by parameters.