Error code

Failure code

Problem

 

Possible causes

 

Remedies

 

 

 

QR

000A

Overvoltage during

The imput voltage fluctuates abnormally.

Insert a suitable input reactor.

 

 

 

 

 

acceleration

(1) The power supply has a capacity of

 

 

 

 

 

 

 

 

 

200kVA or more.

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

 

opened or closed.

 

 

 

 

 

 

 

 

(3) A system using a thyrister is connected

 

 

 

 

 

 

 

 

 

to the same power distribution line.

 

Use H (auto-restart) and H

 

 

 

 

 

 

A restart signal is input to the rotating

 

 

 

 

 

 

 

motor after a momentary stop, etc.

 

(coast stop).

 

 

 

 

 

 

There is possibility of output phase

Check the main circuit output line, motor,

 

 

 

 

 

 

 

failure.

 

etc. for phase failure.

 

 

 

QR

000B

Overvoltage during

The deceleration time FGE is too short.

Increase the deceleration time FGE.

 

 

 

 

 

deceleration

 

(Regenerative energy is too large.)

 

Enable H (overvoltage limit

 

 

 

 

 

 

H (overvoltage limit operation) is

 

 

 

 

 

 

 

off.

 

operation).

 

 

 

 

 

 

The input voltage fluctuates abnormally.

Insert a suitable input reactor.

 

 

 

 

 

 

(1) The power supply has a capacity of

 

 

 

 

 

 

 

 

 

200kVA or more.

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

 

opened and closed.

 

 

 

 

 

 

 

 

(3) A system using a thyrister is connected

 

 

 

 

 

 

 

 

 

to the same power distribution line.

 

Check the main circuit output line, motor,

 

 

 

 

 

 

There is possibility of output phase

 

 

 

 

 

 

 

failure.

 

etc. for phase failure.

 

 

 

QR

000C

Overvoltage during

The input voltage fluctuates abnormally.

Insert a suitable input reactor.

 

 

 

 

 

constant-speed

(1) The power supply has a capacity of

 

 

 

 

 

 

 

operation

 

200kVA or more.

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

 

opened or closed.

 

 

 

 

 

 

 

 

(3) A system using a thyrister is connected

 

 

 

 

 

 

 

 

 

to the same power distribution line.

 

 

 

 

 

 

 

 

The motor is in a regenerative state

 

 

 

 

 

 

 

 

 

because the load causes the motor to run

 

 

 

 

 

 

 

 

 

at a frequency higher than the inverter

 

 

 

 

 

 

 

 

 

output frequency.

Check the main circuit output line, motor,

 

 

 

 

 

 

There is possibility of output phase

 

 

 

 

 

 

 

failure.

 

etc. for phase failure.

 

 

 

QN

000D

Inverter overload

The acceleration time ACC is too short.

Increase the acceleration time CEE.

 

 

 

 

 

 

The DC braking amout is too large.

Reduce the DC braking amount H

 

 

 

 

 

 

The V/F setting is improper.

 

and the DC braking time H.

 

 

 

 

 

 

A restart signal is input to the rotating

Check the V/F parameter setting.

 

 

 

 

 

 

 

motor after a momentary stop, etc.

Use H (auto-restart) and H

 

 

 

 

 

 

The load is too large.

 

(coast stop).

 

 

 

 

 

 

 

 

Use an inverter with a larger rating.

 

 

 

QN

000E

Motor overload

The V/F setting is improper.

Check the V/F parameter setting.

 

 

 

 

 

 

The motor is locked up.

Check the load (operated machine).

 

 

 

 

 

 

Low-speed operation is performed

Adjust QNO to the overload that the

 

 

 

 

 

 

 

continuously.

 

motor can withstand during operation in a

 

 

 

 

 

 

An excessive load is applied to the motor

 

low speed range.

 

 

 

 

 

 

 

during operation.

 

 

 

 

 

*

0020

Over-torque trip

Over-torque reaches to a detection level

Enable H (over-torque trip

13

 

 

 

QV

 

 

 

during operation.

 

selection).

 

 

 

 

 

 

 

Check system error.

 

 

 

 

 

 

 

 

 

 

 

QJ

0010

Overheat

The cooling fan does not rotate.

Restart the operation by resetting the

 

 

 

 

 

 

The ambient temperature is too high.

 

inverter after it has cooled down enough.

 

 

 

 

 

 

The vent is blocked up.

The fan requires replacement if it does

 

 

 

 

 

 

A heat generating device is installed close

 

not rotate during operation.

 

 

 

 

 

 

 

to the inverter.

Secure sufficient space around the inverter.

 

 

 

 

 

 

The thermistor in the unit is broken.

Do not place any heat generating device

 

 

 

 

 

 

 

 

 

near the inverter.

 

 

 

 

 

 

 

 

Make a service call.

*You can select a trip ON/OFF by parameters. (Continued overleaf)