Toshiba VF-FS1 instruction manual Motors

Models: VF-FS1

1 252
Download 252 pages 5.48 Kb
Page 25
Image 25

E6581381

1.4Notes on the application

1.4.1Motors

When the VF-FS1 and the motor are used in conjunction, pay attention to the following items.

Warning

 

 

 

Use an inverter that conforms to the specifications of power supply and three-phase induction motor

 

 

 

 

 

 

being used. If the inverter being used does not conform to those specifications, not only will the three-

Mandatory

phase induction motor not rotate correctly, but it may cause serious accidents through overheating and

fire.

 

 

 

Comparisons with commercial power operation.

The VF-FS1 Inverter employs the sinusoidal PWM system. However, the output voltage and output current are not perfect sine waves, they have a distorted wave that is close to sinusoidal waveform. This is why compared to operation with a commercial power there will be a slight increase in motor temperature, noise and vibration.

Operation in the low-speed area

When running continuously at low speed in conjunction with a general purpose motor, there may be a decline in that motor's cooling effect. If this happens, operate with the output decreased from rated load. To carry out low-speed operation continuously at the rated torque, we recommend to use a inverter rated motor or a forced cooled motor designed for use with an inverter. When operating in conjunction with a inverter rated motor, you must change the inverter's motor overload protection level to VF motor use (QNO).

Adjusting the overload protection level

The VF-FS1 Inverter protects against overloads with its overload detection circuits (electronic thermal). The electronic thermal's reference current is set to the inverter's rated current, so it must be adjusted in line with the rated current of the general purpose motor being used in combination.

High speed operation at and above 60Hz

Operating at frequencies greater than 60Hz will increase noise and vibration. There is also a possibility this will exceed the motor's mechanical strength limits and the bearing limits so you should inquire to the motor's manufacturer about such operation.

Method of lubricating load mechanisms

Operating an oil-lubricated reduction gear and gear motor in the low-speed areas will worsen the lubricating effect. Check with the manufacturer of the reduction gear to find out about operable gearing area.

A-13

1

Page 25
Image 25
Toshiba VF-FS1 instruction manual Motors