trunks. If Ground Start trunks are used, a 55A1 Ground Start Button must be provided at each PFT set.
Only FCC registered
In the event of a Power Failure Transfer (switch has lost power or a major fault has occurred) a contact closure is provided to the Central Office (CO) over a dedicated pair of wires. The CO then makes busy all DID trunks. When power is restored, the closure is removed and the CO restores DID service. External alarm contacts are provided on the front of the ETU for use as required.
Note: It is recommended that customers with Disservice make provisions with their CO to provide this arrangement.
The ETUs are mounted on the
When calculating Unit Loading (see Section 5, “Unit Loads”), all ETU loading counts against Cabinet 1.
The 10B ETU is mounted on the
ETU Power Failure Transfer connections are shown in Figure
Part (b) on Figure
When the system is again able to process calls, normal service is automatically restored.
A multiple ETU arrangement is shown in Figure
control signals from the Call Processor are provided via | legs | 7 and 8 on Octopus cable C2. | ||
The | cable from the Analog “Line” CP | provides | connectivity for eight voice terminals | |
at the Line | input to the ETU. Since the ETU | supports | only | five PFT stations, three of the |
voice terminals are wired straight through the ETU and are not switched during service interruptions. A similar condition exists for the