Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products

Liebert® IntelliSlot® Modbus/BACnet IP 94

3.2 Power Distribution and Power Conditioning Products

Table 33 Liebert Datawave, Liebert FPC, Liebert PPC - Input and Holding - PMP, PM2 Options for

Liebert FPC and Liebert PPC

Controller Power Monitoring Panel - PMP, PM2 Options for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Voltage In X-Y 40001 1 V
Voltage In Y-Z 40002 1 V
Voltage In Z-X 40003 1 V
Voltage Out A-B 40004 1 V
Voltage Out B-C 40005 1 V
Voltage Out C-A 40006 1 V
Voltage Out A-N 40007 1 V
Voltage Out B-N 40008 1 V
Voltage Out C-N 40009 1 V
Current Out A 40010 1 A
Current Out B 40011 1 A
Current Out C 40012 1 A
Ground Current 40013 1 10 A
Neutral Current 40014 1 A
kVA 40015 1 — kVA
kW 40016 1 — kW
Frequency 40017 1 10 Hz
% Capacity A 40018 1 %
% Capacity B 40019 1 %
% Capacity C 40020 1 %
Power Factor 40021 1 100
Kilowatt Hours 1
THD Voltage X 1
THD Voltage Y 1
THD Voltage Z 1
THD Current X 1
THD Current Y 1
THD Current Z 1
K Factor Current X 1
K Factor Current Y 1
K Factor Current Z 1
CREST Factor Current X 1
CREST Factor Current Y 1
CREST Factor Current Z 1