Liebert® IntelliSlot® Modbus/BACnet IP 126Table 44 Liebert APS - Input and Holding
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Protocol
Server Class 30385
1 = UPS
2 = AIR
3 = PMP
4 = PDU
Input
System Input RMS L1-N 30396 1 10 Units : VAC
Uint 16
System Input RMS L2-N 30397 1 10 Units : VAC
Uint 16
System Input RMS L3-N 30398 1 10 Units : VAC
Uint 16
System Input RMS L1-L2 30399 1 10 Units : VAC
Uint 16
System Input RMS L2-L3 30400 1 10 Units : VAC
Uint 16
System Input RMS L3-L1 30401 1 10 Units : VAC
Uint 16
System Input RMS Current L1 30402 1 10 Units : A AC
Uint 16
System Input RMS Current L2 30403 1 10 Units : A AC
Uint 16
System Input RMS Current L3 30404 1 10 Units : A AC
Uint 16
System Input Frequency 30405 1 100 Units : Hz
Uint 16
System Input Power Factor L1 30406 1 100 Uint 16
System Input Power Factor L2 30407 1 100 Uint 16
System Input Power Factor L3 30408 1 100 Uint 16
System Input Brown Out Count 30409 1 Uint 16
System Input Black Out Count 30410 1 Uint 16
Bypass
Bypass Input Voltage RMS L1-N 30421 1 10 Units : VAC
Uint 16
Bypass Input Voltage RMS L2-N 30422 1 10 Units : VAC
Uint 16
Bypass Input Voltage RMS L1-L2 30423 1 10 Units : VAC
Uint 16
Bypass Input Frequency 30424 1 100 Units : Hz
Uint 16
Number Of Transfers To Bypass 30425 1 Uint 16
Bypass Qualification Status 30426 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High