Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 170
UPS Output on Bypass 10177 1 Active on Alarm
Output Load on Maint. Bypass 10178 1 Active on Alarm
Backfeed Breaker Open 10179 1 Active on Alarm
Auto Restart In Progress 10180 1 Active on Alarm
Power Supply Failure 10181 1 Active on Alarm
Auto Restart Inhibited - Ext 10183 1 Active on Alarm
Automatic Restart Failed 10184 1 Active on Alarm
Main Controller Fault 10185 1 Active on Alarm
Fuse Failure 10186 1 Active on Alarm
System Controller Error 10187 1 Active on Alarm
System Breaker(s) Open Failure 10188 1 Active on Alarm
System Breaker(s) Close Failure 10189 1 Active on Alarm
Input Filter Cycle Lock 10190 1 Active on Alarm
EMO Shutdown 10191 1 Active on Alarm
Service Code Active 10192 1 Active on Alarm
LBS Active 10193 1 Active on Alarm
LBS Inhibited 10194 1 Active on Alarm
Regeneration Active 10195 1 Active on Alarm
Regeneration Operation Terminated 10196 1 Active on Alarm
Regeneration Operation Failure 10197 1 Active on Alarm
Leading Power Factor 10198 1 Active on Alarm
Controls Reset Required 10199 1 Active on Alarm
MultiModule
Loss of Redundancy 10212 1 Active on Alarm
MMS Overload 10215 1 Active on Alarm
MMS On Battery 10216 1 Active on Alarm
MMS Module Alarm Active 10218 1 Active on Alarm
Program Input Signals
Program Input Contact 01 10229 1 Active on Alarm
Program Input Contact 02 10230 1 Active on Alarm
Program Input Contact 03 10231 1 Active on Alarm
Program Input Contact 04 10232 1 Active on Alarm
Program Input Contact 05 10233 1 Active on Alarm
Program Input Contact 06 10234 1 Active on Alarm
Program Input Contact 07 10235 1 Active on Alarm
Program Input Contact 08 10236 1 Active on Alarm
Program Input Contact 09 10237 1 Active on Alarm
Program Input Contact 10 10238 1 Active on Alarm
Program Input Contact 11 10239 1 Active on Alarm
Program Input Contact 12 10240 1 Active on Alarm
Intelligent Paralleling
IP Inhibit 10251 1 Active on Alarm
ECO Mode
ECO Mode Active 10262 1 Active on Alarm
ECO Mode Suspended 10263 1 Active on Alarm
Excess ECO Suspends 10264 1 Active on Alarm
Table 58 Liebert NXL - 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description Stat us Coil
Number
of Bits Notes / Units