BACnet Communications - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 300
Power Sub Module Fault Binary_Value 51 5158_1 RD Active on Alarm
Battery Discharging Binary_Value 52 4168_1 RD Active on Alarm
UPS Output on Bypass Binary_Value 53 4298_1 RD Active on Alarm
Output Load on Maint. Bypass Binary_Value 54 4299_1 RD Active on Alarm
Battery Capacity Low Bi nary_Value 55 4166 _1 RD Active on Alarm
MMS On Battery Binary_Value 56 4834_1 RD Active on Alarm
Redundancy Binary_Value 57 4825_1 RD Active on Alarm
Top Outlet Fan Fault Binary_Value 58 5770_1 RD Active on Alarm
MMS Over Capacity Binary_Value 59 5771_1 RD Active on Alarm
Table 98 Liebert APM, Liebert NXC, Liebert NXR - Binary Data (continued)
Data Label Object Type Instance
Object
Name Access Notes