Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert® IntelliSlot® Modbus/BACnet IP 100Table 36 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX - Input and Holding
Controller Liebert iCOM® v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Input Power 1
Input Voltage A-B 30385 1 VAC
Input Voltage B-C 30386 1 VAC
Input Voltage C-A 30387 1 VAC
Input Power 2
Input Voltage A-B 30391 1 VAC
Input Voltage B-C 30392 1 VAC
Input Voltage C-A 30393 1 VAC
Output Power 1 ——
Output Voltage X-Y 30397 1 VAC
Output Voltage Y-Z 30398 1 VAC
Output Voltage Z-X 30399 1 VAC
Output Voltage Vx 30400 1 VAC
Output Voltage Vy 30401 1 VAC
Output Voltage Vz 30402 1 VAC
Output Current Ix 30403 1 A AC
Output Current Iy 30404 1 A AC
Output Current Iz 30405 1 A AC
Output Neutral Current 30406 1 A AC
Ground Current 30407 1 10 A AC
Output Frequency 30408 1 Hz
Output Power (kVA) 30409 1 kVA
Output Power (kW) 30410 1 kW
Output kW-Hrs 30411 40411 2 kWH
Output Power Factor 30413 1 100
Output Percent Load 30414 1 %
Output Voltage Vx THD 30415 1 10 % THD
Output Voltage Vy THD 30416 1 10 % THD
Output Voltage Vz THD 30417 1 10 % THD
Output Current Ix THD 30418 1 10 % THD
Output Current Iy THD 30419 1 10 % THD
Output Current Iz THD 30420 1 10 % THD
Output Current Ix K-Factor 30421 1 10
Output Current Iy K-Factor 30422 1 10
Output Current Iz K-Factor 30423 1 10
Output Current Ix Crest Factor 30424 1 10
Output Current Iy Crest Factor 30425 1 10
Output Current Iz Crest Factor 30426 1 10