BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 298Table 97 Liebert Mini-Mate2 8 Ton - L8T
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Data Description BACnet Instance Notes
Status Points (View)
Temperature BS01_x
Humidity BS02_x —
Cooling BS03_x 1=On / 0=Off
Heating BS04_x 1=On / 0=Off
Humidification BS05_x 1=On / 0=Off
De-humidification BS06_x 1=On / 0=Off
Econ-O-Cycle BS07_x 1=On / 0=Off
Stages BS08_x —
% Capacity BS09_x
Unit Status (On / Off) BS18_x 1=On / 0=Off
Alarm Points
Communications BA01_x:00
Local Off BA01_x:01
Remote Off BA01_x:02
High Head Pressure 1 BA01_x:03
High Head Pressure 2 BA01_x:04
Loss of Airflow BA01_x:05
Standby Glycol Unit On BA01_x:06
Change Filters BA01_x:08
High Temperature BA01_x:09
Low Temperature BA01_x:10
High Humidity BA02_x00
Low Humidity BA02_x01
Humidifier Problem BA02_x02
Smoke Detected BA02_x:08
Loss of Water BA02_x:09
Standby Unit On BA02_x:10
Short Cycle BA03_x:01
Loss of Power BA03_x:02
Local Alarm 1 BA03_x:06
Local Alarm 2 BA03_x:07
High Water Humidifier Pan BA03_x:08
Setpoints (View)
Temperature Setpoint BS10_x
Humidity Setpoint BS12_x
Control Points (Set)
Unit On / Off BC01_x Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint BC02_x -
Temperature Tolerance BC02_x Multiply desired value by 1000
Humidity Setpoint BC03_x -
Humidity Tolerance BC03_x Multiply desired value by 1000
Reheat Lockout BC01_x Bit 2 on=RH off Bit 3 on=RH on
Humidifier Lockout BC01_x Bit 4 on=HL off Bit 5 on=HL on