Modbus 485 and Modbus IP Protocols - Thermal Management Products
81 Liebert® IntelliSlot® Modbus/BACnet IPTable 25 Liebert XDF - Status and Coil
Controller Liebert iCOM® v3
Data Description Stat us Coil
Number
of Bits Scale Notes / Units
Temperature Indication110011 11 1
Unit Control 25 1
Reset Alarm 26 1
Acknowledge Alarm 27 1
Cabinet Sensor Alarm Enable 10023 23 1
Fan On 10025 1
Cool On 10026 1
Compressor 1 High Pressure 10037 1
Compressor 1 Low Pressure 10038 1
Cond Pump-High Water 10052 1
Loss Compressor Power 10054 1
Emergency Damper Fail 10056 1
High Internal Temperature 10057 1
Loss of Power 10061 1
Remote Shutdown 10062 1
Unspecified Event(s) 110064 — 1
Unit Hrs Exceeded 10080 1
Comp 1 Hrs Exceeded 10081 1
Network Failure 10091 1
No Connection W/Unit 1 10092 1
Unit(s) Disconnected 10093 1
Unit Code Missing 10094
Unit Code Mismatch 10095
Low Memory 1 10097
Ram / Battery Failure 10098
(Parallel Flash) MEMORY 1 FAIL 10100
(Serial Flash) MEMORY 2 FAIL 10101
Front Door Open 10102
Rear Door Open 10103
Digital Scroll Compressor 1 Sensor Fail 10108
Low Int Temperature 10110
High Ext Dewpoint 10111
Cabinet Temp Sensor Fail 10112
Cabinet Humidity Sensor Fail 10113
Ambient Temp Sensor Fail 10114
Comp 1 Short Cycle 10132
Reheat Lockout 10140
Humidifier Lockout 10141
Compressor(s) Lockout 10142
Backup Ventilation 10143
Door Open 10144
Device Load 10146
Alarm Status 10147
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event.