Modbus 485 and Modbus IP Protocols - Thermal Management Products
29 Liebert® IntelliSlot® Modbus/BACnet IP
Customer Input 4 - Event Control
Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Customer Input 4 - Event Type The event type for the [Customer Input 4] event.
Customer Input 4 Customer Input 4
Dehumidifier Hours Exceeded Operating hours for the dehumidifier have exceeded the threshold.
Dehumidifier Hours Threshold Threshold value used in the [Dehumidifier Hours Exceeded] event.
Dehumidifier Hours
Operating hours for dehumidifier since last reset of this value. If operating hours
exceeds 32,000, this client will continue to display 32,000, but the iCOM display will
show the actual value.
Dehumidifier State Dehumidifier operational state.
Dehumidifier Utilization Present dehumidifier utilization expressed as a percentage of the maximum rated
capacity.
Dew Point Over Temperature Dew point temperature reading has exceeded the upper threshold.
Dew Point Set Point Desired dew po int temperature.
Dew Point Under Temperature Dew point temperature reading has dropped below the lower threshold.
Dig Scroll Comp Discharge Over
Temp - Event Ctrl Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp] event.
Dig Scroll Comp Discharge Over
Temp - Event Type The event type for the [Dig Scroll Comp Discharge Over Temp] event.
Dig Scroll Comp Discharge Temp
Sensor Issue
Digital scroll compressor discharge temperature sensor is disconnected or the signal
is out of range.
Dig Scroll Comp Discharge Temp Digital scroll compressor discharge temperature.
Dig Scroll Comp Over Temp Digital scroll compressor is shut down due to head temperature exceeding an upper
threshold.
Digital Output Board Not Detected Digital output board is required to be connected, but no signal is dete cted.
Digital Scroll Compressor Loading Present digital scroll compressor utilization expressed as a percentage of the
maximum rated capacity.
EEV Unspecified General Event One or more unspecified electronic expansion valve events active. See local unit
display for further details.
Electric Reheat State Electric reheater operational state.
Electric Reheater Hours Exceeded [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
Electric Reheater Hours Threshold Threshold value used in the [Electric Reheater Hours Exceeded] event.
Electric Reheater Hours
Operating hours for electric reheater since last reset of this value. If operating hours
exceeds 32,000, this client will continue to display 32,000, but the iCOM display will
show the actual value.
Energy Consumption Energy consumption since the last reset of this value.
Ext Air Damper Position Issue Air damper po sition does not match expected value, as indicated by an external input
signal.
Ext Air Sensor A Dew Point Temp Dew point temperature as measured by external air sensor A.
Ext Air Sensor A Event Control Enable/disable the activation of events related to measurements by the external air
sensor A.
Ext Air Sensor A High Humidity -
Event Control
Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext Air Sensor A High Humidity -
Event Type The event type for the [Ext Air Sensor A High Humidity] event.
Table 10 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Glossary (continued)
Controller Liebert iCOM® v4
Data Label Data Description