Modbus 485 and Modbus IP Protocols - Thermal Management Products
93 Liebert® IntelliSlot® Modbus/BACnet IP
Humidity Low Level 40290 1 Bit 4
Battery Level Low 40290 1 Bit 5
Loss of Power 40290 1 Bit 6
Local Alarm 1 40290 1 Bit 7
Local Alarm 2 40290 1 Bit 8
Cool 3 Low Pressure 40290 1 Bit 9
Cool 4 Low Pressure 40290 1 Bit 10
Cool 3 High Pressure 40290 1 Bit 11
Cool 4 High Pressure 40290 1 Bit 12
Air Flow 2 Loss 40290 1 Bit 13
Setpoints (View)
Return Air Temperature 40016 1 10 deg C (R/W)
Return Air Humidity 40017 1 10 deg C (R/W)
Supply Air Temperature 40018 1 10 deg C (R/W)
High Temp Alarm 40025 1 10 deg C (R/W)
Low Temp Alarm 40026 1 10 deg C (R/W)
High Hum Alarm 40027 1 10 % (R/W)
Low Hum Alarm 40028 1 10 % (R/W)
Restart Delay 40029 1 Seconds (R/W)
Control Points (Set)
Activation Mode 40006 1 1=On / 0=Off (R/W)
General Alarm Status 40022 1 1=On / 0=Off; write 0 to reset alarm
Audible Alarm Status 40023 1 1=On / 0=Off; write 0 to ack alarm
Return Air Temperature 40349 1 10 deg C (R/W)
Return Air Humidity 40350 1 10 deg C (R/W)
Supply Air Temperature 40351 1 10 deg C (R/W)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 32 Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100 - Input and Holding - C100 4-step
Controller CEMS 100
Liebert Products
Liebert Atlas Air
Liebert Atlas PEC
Liebert CEMS 100
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units