Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 20
Ext Air Sensor A Low Humidity - Event
Control 30357 40357 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Ext Air Sensor A Low Humidity - Event Type 30358 40358 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A Over Temp - Event Control 30359 4 0359 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Ext Air Sensor A Over Temp - Event Type 30360 40360 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A Under Temp - Event
Control 30361 40361 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Ext Air Sensor A Under Temp - Event Type 30362 40362 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
High Return Humidity - Event Control 30363 4 0363 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
High Return Humidity - Event Type 30364 40364 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Low Return Humidity - Event Control 30365 40365 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Low Return Humidity - Event Type 30366 40366 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Return Air Over Temp - Event Control 30367 40367 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Return Air Over Temp - Event Type 30368 40368 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Return Air Under Temp - Event Control 30369 40369 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Return Air Under Temp - Event Type 30370 40370 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Fan Hours Exceeded - Event Control 30371 40371 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Fan Hours Exceeded - Event Type 30372 4 0372 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Fan Issue - Event Control 30373 40373 1 0 = disabled
1 = enabled 1
Fan Issue - Event Type 30374 40374 1
0 = Message
1 = Warning
2 = Alarm
1
Main Fan Overload - Event Control 30375 40375 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Main Fan Overload - Event Type 30376 40376 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra