Modbus 485 and Modbus IP Protocols - UPS Systems
177 Liebert® IntelliSlot® Modbus/BACnet IP
Module Output Breaker 30609 1
0 = Open
1 = Close
2 = Not Installed
MultiModule
Multi-module System Output Voltage RMS A-B 30620 1 10 Units : VAC
Uint16
Multi-module System Output Voltage RMS B-C 30621 1 10 Units : VAC
Uint16
Multi-module System Output Voltage RMS C-A 30622 1 10 Units : VAC
Uint16
Multi-module System Output Voltage RMS A-N 30623 1 10 Units : VAC
Uint16
Multi-module System Output Voltage RMS B-N 30624 1 10 Units : VAC
Uint16
Multi-module System Output Voltage RMS C-N 30625 1 10 Units : VAC
Uint16
Sum of MMS Output RMS Currents for Phase A 30626 1 Units : A AC
Uint16
Sum of MMS Output RMS Currents for Phase B 30627 1 Units : A AC
Uint16
Sum of MMS Output RMS Currents for Phase C 30628 1 Units : A AC
Uint16
MMS Output Frequency 30629 1 10 Units : Hz
Uint16
MMS Output Power 30630 1 Units : kW
Uint16
MMS Output Apparent Power 30631 1 Units : kVA
Uint16
MMS Output Power Factor Phase A 30632 1 100 Int16
MMS Output Power Factor Phase B 30633 1 100 Int16
MMS Output Power Factor Phase C 30634 1 100 Int16
MMS Output Pct Power Phase A 30635 1 Units : %
Int16
MMS Output Pct Power Phase B 30636 1 Units : %
Int16
MMS Output Pct Power Phase C 30637 1 Units : %
Int16
MMS Output Pct Apparent Pwr (kVA) Phase A 30638 1 Units : %
Uint16
MMS Output Pct Apparent Pwr (kVA) Phase B 30639 1 Units : %
Uint16
MMS Output Pct Apparent Pwr (kVA) Phase C 30640 1 Units : %
Uint16
Number of Redundant Modules 30641 1 Uint16
MMS Module Number 30642 1 Int16
Number of Modules in a MMS 30643 1 Uint16
Module Output Breaker for Module 1 30644 1
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 2 30645 1
0 = Open
1 = Close
2 = Not Installed
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label Input Holding # of Reg Scale Notes/Units