BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 266
Condenser Low Noise Mode Stop Time The time of day at which the condenser will transition out of low noise mode.
Condenser Max Fan Speed Override Fan speed exceeding the maximum set po int in order to alleviate a high
temperature or pressure condition.
Condenser Normal Mode Max Fan
Speed Maximum fan speed when condenser is not in low noise mode.
Condenser Outside Air Temp Out of
Operating Range
[Condenser Outside Air Temperature] is either above an upper threshold or
below a lower threshold.
Condenser Outside Air Temp Sensor
Issue
Condenser outside air temperature sensor is disconnected or the signal is out of
range.
Condenser Outside Air Temperature Condenser ambient outside air temperature.
Condenser Refrigerant Pressure Over
Threshold Condenser refrigerant pressure has exceeded a threshold.
Condenser Refrigerant Pressure Sensor
Issue
Condenser refrigerant pressure sensor is disconnected or the signal is out of
range.
Condenser Refrigerant Pressure Under
Threshold Condenser refrigerant pressure has dropped below a threshold.
Condenser Refrigerant Type Condenser refrigerant type.
Condenser Supply Refrigerant Over
Temp Condenser supply refrigerant temperature has exceeded a threshold.
Condenser Supply Refrigerant Temp
Sensor Issue
Condenser supply refrigerant temperature sensor is disconnected or the signal
is out of range.
Condenser Supply Refrigerant Under
Temp
Condenser supply refrigerant temperature has dropped below a specified
threshold.
Condenser TVSS Issue - Event Control
Enable/disable the activation of the [Condenser TVSS Issue] event (Transient
Voltage Surge Suppressor). If set to 'disabled', the event will not be annunciated.
This implies that the event will not be placed in any active event list or in any
event history list.
Condenser TVSS Issue - Event Type The event type for the [Condenser TVSS Issue] event (Transient Voltage Surge
Suppressor).
Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor device has failed.
Condenser Unit Unspecified General
Event
One or more unspecified condenser unit events active. See local unit display for
further details.
Condenser VFD Issue - Event Control
Enable/disable the activation of the [Condenser VFD Issue] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Condenser VFD Issue - Event Type The event type for the [Condenser VFD Issue] event.
Condenser VFD Issue The condenser fan Variable Frequency Drive is offline.
Cooling Capacity (Primary) Compressor utilization or chilled water valve position, based on unit type.
Cooling Proportional Band Temperature control band above [Air Temperature Set Point]. If measured air
temperature is within this band, cooling operations are proportionally controlled.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Customer Input 1 - Event Type The event type for the [Customer Input 1] event.
Customer Input 1 Customer Input 1.
Customer Input 2 - Event Control
Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Customer Input 2 - Event Type The event type for the [Customer Input 2] event.
Customer Input 2 Customer input 2.
Customer Input 3 - Event Control
Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Table 86 Liebert CRV - Glossary (continued)
Data Label Data Description