BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 242
Low Return Humidity - Event
Type MultiState_Value 237 5140_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Return Air Over Temp - Event
Control MultiState_Value 238 5024_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Return Air Over Temp - Event
Type MultiState_Value 239 5025_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Return Air Under Temp - Event
Control MultiState_Value 240 5407_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Return Air Under Temp - Event
Type MultiState_Value 241 5408_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Supply Air Over/Under
Temperature - Event Control MultiState_Value 242 5587_1_1 RW 1 = disabled
2 = enabled
2, 3, 4,
5, 6
System Event Configuration - Fan
Fan Hours Exceeded - Event
Control MultiState_Value 252 5409_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Fan Hours Exceeded - Event
Type MultiState_Value 253 5410_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Fan Issue - Event Control MultiState_Value 254 4730_1_1 RW 1 = disabled
2 = enabled 1
Fan Issue - Event Type MultiState_Value 255 4731_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1
Main Fan Overload - Event
Control MultiState_Value 256 5411_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Main Fan Overload - Event
Type MultiState_Value 257 5412_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
System Event Configuration - Condenser
Condenser Issue - Event
Control MultiState_Value 268 5413_1_1 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Condenser Issue - Event Type MultiState_Value 269 5414_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
System Event Configuration - Condenser
Condenser Issue - Event
Control MultiState_Value 280 5413_1_2 RW 1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Condenser Issue - Event Type MultiState_Value 281 5414_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
System Events
System Event Acknowledge/
Reset MultiState_Value 292 4717_1 WO 1 = Reset
2 = Acknowledge
1, 2, 3,
4, 5, 6
Compressors
Compressor Lockout MultiState_Value 304 5580_1 RW 1 = disabled
2 = enabled
2, 3, 4,
5, 6
Table 80 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Multistate Data (continued)
Data Label Object Type Instance Object Name Access Notes
Extra
Notes