BACnet Communications - Thermal Management Products
271 Liebert® IntelliSlot® Modbus/BACnet IPTable 87 Liebert HPC - Binary Data
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes
Extra
Notes
Compressors
Compressor Not Stopping Binary_Value 1 5263_1 RD Active on Alarm 1, 2
Compressor Superheat Over Threshold Binary_Value 2 5604_1 RD Active on Alarm 2
Compressors - Compressor 1
Compressor Hours Exceeded Binary_Value 12 5269_1_1 RD Active on Alarm 1, 2
Compressor High Head Pressure Binary_Value 13 5270_1_1 RD Active on Alarm 1 , 2
Compressor Low Suction Pressure Binary_Value 14 5271_1_1 RD Active on Alarm 1, 2
Compressor Thermal Overload Binary_Value 15 5272_1_1 RD Active on Alarm 1, 2
Compressor Low Oil Pressure Bin ary_Value 16 5273_1_1 RD Active on Alarm 1, 2
Compressor Loss of Differential Pressure Binary_Value 17 5275_1_1 RD Active on Alarm 1, 2
Compressor Capacity Reduced Binary_Value 18 5513_1_1 RD Active on Alarm 1, 2
Compressor Capacity Normal Binary_Value 19 5773_1_1 RD Active on Alarm 2
Compressor Contactor Issue Binary_Value 20 5774_1_1 RD Active on Alarm 2
Compressors - Compressor 2
Compressor Hours Exceeded Binary_Value 29 5269_1_2 RD Active on Alarm 1, 2
Compressor High Head Pressure Binary_Value 30 5270_1_2 RD Active on Alarm 1 , 2
Compressor Low Suction Pressure Binary_Value 31 5271_1_2 RD Active on Alarm 1, 2
Compressor Thermal Overload Binary_Value 32 5272_1_2 RD Active on Alarm 1, 2
Compressor Low Oil Pressure Bin ary_Value 33 5273_1_2 RD Active on Alarm 1, 2
Compressor Loss of Differential Pressure Binary_Value 34 5275_1_2 RD Active on Alarm 1, 2
Compressor Capacity Reduced Binary_Value 35 5513_1_2 RD Active on Alarm 1, 2
Compressor Capacity Normal Binary_Value 36 5773_1_2 RD Active on Alarm 2
Compressor Contactor Issue Binary_Value 37 5774_1_2 RD Active on Alarm 2
Compressors - Compressor 4
Compressor Hours Exceeded Binary_Value 263 5269_1_4 RD Active on Alarm 2
Compressor High Head Pressure Binary_Value 264 5270_1_4 RD Active on Alarm 2
Compressor Low Suction Pressure Binary_Value 265 5271_1_4 RD Active on Alarm 2
Compressor Thermal Overload Binary_Value 266 5272_1_4 RD Active on Alarm 2
Compressor Low Oil Pressure Bin ary_Value 267 5273_1_4 RD Active on Alarm 2
Compressor Loss of Differential Pressure Binary_Value 268 5275_1_4 RD Active on Alarm 2
Compressor Capacity Reduced Binary_Value 269 5513_1_4 RD Active on Alarm 2
Compressor Capacity Normal Binary_Value 270 5773_1_4 RD Active on Alarm 2
Compressor Contactor Issue Binary_Value 271 5774_1_4 RD Active on Alarm 2
Condenser 1
Condenser Fan Issue Binary_Value 46 5277_1 RD Active on Alarm 1 , 2
Low Condenser Refrigerant Pressure Binary_Value 47 5278_1 RD Active on Alarm 1, 2
Condenser Max Fan Speed Override Binary_Value 48 5545_1 RD Active on Alarm 1, 2
Condenser 2
Condenser Fan Issue Binary_Value 59 5277_2 RD Active on Alarm 1 , 2
Low Condenser Refrigerant Pressure Binary_Value 60 5278_2 RD Active on Alarm 1, 2
Condenser Max Fan Speed Override Binary_Value 61 5545_2 RD Active on Alarm 1, 2
Condenser 4
Condenser Fan Issue Binary_Value 67 5277_4 RD Active on Alarm 2
Low Condenser Refrigerant Pressure Binary_Value 68 5278_4 RD Active on Alarm 2
Fluid
Low Fluid Pressure Binary_Value 72 5280_1 RD Active on Alarm 1, 2
Return Fluid Temp Sensor Issue Binary_Value 73 5295_1 RD Active on Alarm 1, 2