BACnet Communications - UPS Systems
341 Liebert® IntelliSlot® Modbus/BACnet IP
Tabl e 110 Lie ber t NXL - 50 Hz, CE version (Models 48 and 49)—Binary Data
Data Label
Object
Type Instance
Object
Name Access Notes
Input
System Input Power Problem Binary_Value 1 4122_1 RD Active on Alarm
System Input Phs Rotation Error Binary_Value 2 4146_1 RD Active on Alarm
System Input Current Limit Binary_Value 3 414 7_1 RD Active on Alarm
System Input Current Imbalance Bina ry_Value 4 4382_1 RD Active on Alarm
Bypass
Bypass Not Available Binary_Value 15 4135_1 RD Active on Alarm
Bypass Overload Phase A Binary_Value 16 4132_1 RD Active on Alarm
Bypass Overload Phase B Binary_Value 17 4133_1 RD Active on Alarm
Bypass Overload Phase C Binary_Value 18 4134_1 RD Active on Alarm
Bypass Auto Retransfer Failed Binary_Value 19 4138_1 RD Active on Alarm
Bypass Static Switch Overload Binary_Value 20 4142_1 RD Active on Alarm
Bypass Static Switch Unavailable Binary_Value 21 4143_1 RD Active on Alarm
Bypass Auto Transfer Failed Binary_Value 22 4145_1 RD Active on Alarm
Bypass Frequency Error Binary_Value 23 4175_1 RD Active on Alarm
Bypass - Manual Rexfr Inhibited Binary_Value 24 4218_1 RD Active on Alarm
Bypass - Manual Xfr Inhibited Binary_Value 25 4217_1 RD Active on Alarm
Battery
Battery Automatic Test Inhibited Binary_Value 36 4740_1 RD Active on Alarm
Battery Capacity Low Binary_Value 37 4166_1 RD Active on Alarm
Battery Discharging Binary_Value 38 4168_1 RD Active on Alarm
Battery Temperature Imbalance Binary_Value 39 4169_1 RD Active on Alarm
Battery Equalize Binary_Value 40 4170_1 RD Active on Alarm
Battery Auto Test In Progress Binary_Value 41 4172_1 RD Active on Alarm
Main Battery Disconnect Open Binary_Value 42 4173_1 RD Active on Alarm
Battery Low Binary_Value 43 4162_1 RD Active on Alarm
Battery Temperature Sensor Fault Binary_Value 44 4174_1 RD Active on Alarm
Battery Circuit Breaker 1 Open Binary_Value 45 4176_1 RD Active on Alarm
Battery Circuit Breaker 2 Open Binary_Value 46 4179_1 RD Active on Alarm
Battery Circuit Breaker 3 Open Binary_Value 47 4182_1 RD Active on Alarm
Battery Circuit Breaker 4 Open Binary_Value 48 4185_1 RD Active on Alarm
Battery Circuit Breaker 5 Open Binary_Value 49 4188_1 RD Active on Alarm
Battery Circuit Breaker 6 Open Binary_Value 50 4191_1 RD Active on Alarm
Battery - External Monitor 1 Binary_Value 51 4220_1 RD Active on Alarm
Battery - External Monitor 2 Binary_Value 52 4221_1 RD Active on Alarm
Battery Ground Fault Binary_Value 53 4222_1 RD Active on Alarm
Battery Over Temperature Limit Binary_Value 54 5871_1 RD Active on Alarm
Battery Low Shutdown Binary_Value 55 4742_1 RD Active on Alarm
Battery Over Temperature Binary_Value 56 4219_1 RD Active on Alarm
Battery Test Failed Binary_Value 57 4323_1 RD Active on Alarm
Unexpected Main Battery Disconnect Closure Binary_Value 58 5873_1 RD Active on Alarm
Battery Over Voltage Binary_Value 59 5874_1 RD Active on Alarm
Battery Fuse Fault Binary_Value 60 5875_1 RD Active on Alarm
Main Battery Disconnect Forced To Unlock Binary_Value 61 5878_1 RD Active on Alarm